Hazard information
The actuator is part of the building installation.
The relevant national standards and directives
must be taken into consideration during planning
and set-up. The device has been designed solely
for operation on a 230V/50 Hz AC supply. Only
qualified electricians (to VDE 0100) are permitted
to carry out work on the 230 V mains. Applicable
accident prevention regulations must be com-
plied with whilst such work is being carried out.
To avoid electric shocks from the device, please
disconnect the
mains voltage (trip the miniature
circuit-breaker).
Noncompliance with the instal-
lation instructions can cause fire or introduce
other hazards.
When connecting to the device terminals, take
the permissible cables and cable cross sections
into account.
The circuit to the which the device will be
connected has to be secured by a cable
protection switch in accordance with EN60898-1
(tripping characteristic B or C, max. 16 A rated
current, min. 6 kA interrupting rating, energy
limiting class 3). Installation regulations according
to VDE 0100 and HD382 or 60364 have to be
considered. Users must be able to easily access
the cable protection switch. This must be marked
as disconnecting device for the actuator.