CTP Series Installation, Operation & Maintenance Manual Project: _________________________ Installation: ___________________ Pump Model: ____________ Serial Number: ___________ PN# CTPIOM 7/08 390 Birmingham Boulevard y Ansonia, CT 06401
CTP Series GENERAL INSTRUCTIONS: This manual is intended to provide basic installation and start-up guidance. It is to be read and thoroughly studied prior to attempting to install or operate any of the equipment supplied. Equipment damage, which occurs by not following these instructions, will void the warranty. SAFETY PRECAUTIONS: Only trained qualified personnel shall be utilized for installation and start-up.
CTP Series ELECTRICAL INSTALLATION: GENERAL GUIDELINES All electrical work shall be carried out under the supervision of an authorized, licensed electrician. The present state adopted edition of the National Electrical Code as well as all local codes and regulations shall be complied with. VERIFICATION OF POWER SUPPLY Prior to making any electrical connections or applying power to the pump, compare the power supply available at the pump station to the data on the unit's nameplate.
CTP Series MECHANICAL INSTALLATION: PUMPS WITH AUTOCOUPLING SYSTEMS The HOMA Auto-Coupling is a quick removal system used in keeping personnel from having to enter the wet well. The pump mounts on a stationary base and operates completely or partially submerged (min. 8” above volute) in the pumping media. The HOMA Auto-Coupling kit includes a base elbow, guide claw flange and upper guide rail bracket. Kit also includes a profile seal and base anchor bolts. Refer to dimensional drawing for details.
CTP Series START-UP Install lifting chain or cable of adequate size and load rating of the unit. Allow for proper length to permit proper lowering and raising of the pump. Properly position power cables and lifting devise over the load and keep them from entering the pump suction. Prior To Installation: Before lowering the pump into position check the direction of rotation. The impeller will rotate clockwise as viewed from the top.
CTP Series Installation / Startup Troubleshooting: Listing of Possible Causes: Only authorized service personnel who are trained professionals shall troubleshoot and repair pumps that are experiencing operational or performance difficulties. All HOMA pumps are factory tested, yet startup difficulties can occur with any mechanical equipment. Please note that our technical support staff stands ready to assist you with any problem or difficulty you might encounter with our equipment.
CTP Series PREVENTIVE MAINTENANCE Regular preventive maintenance will help ensure longer pump life and more reliable operation. It is recommended that pumps in intermittent operation be inspected twice a year and pumps in continuous operation be inspected every 1,000 hours. The following is a listing of required inspection and maintenance items. If any of the problems described in the following list exists stop operating the pump to avoid damage or personal injury. 5.
CTP Series PROFILE SEAL INSTALLATION IMPORTANT Black Rubber Sealing Ring (Profile Seal) must be installed in the Guide Claw before pump is installed. Ring must be installed with the large diameter lip inside the groove of the Guide Claw Flange. CALL OUR TECHNICAL SUPPORT GROUP WITH ANY QUESTIONS REGARDING THE INSTALLATION OF THIS EQUIPMENT. Pg.
CTP Series SEAL PROBE INSTALLATION PROCEDURE Mechanical Seal Leak Detection probe has been loose to protect from shipping damage. Please follow this procedure to install the probe. 1) Lay pump on its side with the plug on the seal chamber facing upwards as indicated. 2) Unscrew the plug with the proper wrench, taking care not to damage the sealing surface. 3) Verify that seal chamber oil level is within ¼” of the indicated value. Measurement is from oil level to the top of hole.
CTP Series CTP Series 3 Phase Connection Diagram 4 Conductor Cable 7 Conductor Cable FM 7 Conductor Cable (Standard) 10 Conductor Cable Ground Lug - For auxiliary grounding to earth or grounding grid. Pg.
CTP Series START-UP REPORT This report is designed to insure the customer that customer service and a quality product are the number one priority with HOMA Pump Technology, Inc. Please answer the following questions completely and as accurately as possible. Mail this form to: HOMA PUMP TECHNOLOGY INC. 390 BIRMINGHAM BOULEVARD ANSONIA, CT 06401 ATTN: SERVICE MANAGER Receipt of completed report will initiate operational warranty. Reports that are not returned can delay or void warranty. 1.
CTP Series 7.