Installation Of HOMA GRP Pump On 2,5 Myers Rail Systems User guide

Publication
88PN3030A
Please Contact
Technical Support
At 203
-
736
-
8890 With Any Additional Questions
Please Be Prepared To Provide Pump Serial Number During Call
Page
1 of 2
Conversion Kit For Installation of HOMA
GRP Pumps On 2½” Myers Rail
Systems
Use existing Myers hardware to connect the HOMA pump to the Myers rail system
following the procedure below.
Thread the 2” X 2 ½” bushing fully onto the discharge of the new HOMA pump after
applying red thread locking compound.
After applying red thread locking compound, thread the flange threads onto the male
threads of the bushing. Tighten fully until two of the flange bolt holes are in a
horizontal position.
Align and fasten the flange to the Myers bracket using existing bolts and new gasket
provided. Tighten the bolts equally. If existing bolts are damaged, obtain qty (4) new
5/8”-11 x 1 1/2”bolts.
Remove the pump handle from the HOMA pump and rotate the handle 180
0
so that
the high side of the handle is on the same side as the pump discharge connection,
and reattach.
Thread locking cap onto the threaded portion of the support column. Thread
together
loosely as the cap will be used for final adjustment.
Slide the support column down through the upper bracket of the Myers rail system
so that the notch is over the handle of the HOMA pump.