Install Instructions

Before using this product read and understand instructions.
Save these instructions for future reference.
All work must be performed by qualified personnel trained in the proper application,
installation, and maintenance of plumbing, steam, and electrical equipment and/or systems in
accordance with all applicable codes and ordinances.
Turn off steam supply before installing or servicing.
Open supply valves slowly to prevent water hammer or sudden shock.
Wear heat resistant gloves before adjusting steam valves.
Handle regulator with extreme caution. Do not lift regulator by any external tubing.
Failure to follow this warning may result in property damage, serious burns, personal injury
or death.
W
ARNING
CAUTION
!
WARNING
Series SPS Spring Pilots
For Series 2000 Pilot-Operated
Regulators
Series SPS Spring Pilots
The Series SPS Spring Pilot Control Valve senses and balances
downstream pressure against an adjustable spring to control a
Series 2000 Pilot Operated Regulator main valve and thus regu-
late downstream pressure to a set point. The Series 2000
Regulator reduces a steady or varying inlet pressure to a con-
stant, adjustable delivery pressure.
The Series SPS pilots are spring loaded. Normal accuracy of
regulation is within 10% of set point. The adjustable range of the
delivery pressure is governed by the choice of adjusting spring
as shown below.
Pressure Wire
Range Spring Diameter
psig (bar) Color in. (mm)
2-30 (0.1-2.0) Blue
3
16 (4)
5-60 (0.3-4.1) Red
1
4 (6)
20-175 (1.4-11.9) Gold
11
32 (9)
Hoffman Specialty
Installation & Maintenance
Instructions
HS-621(A)

Summary of content (6 pages)