Install Instructions
• Before using this product read and understand instructions.
• Save these instructions for future reference.
• All work must be performed by qualified personnel trained in the proper application,
installation, and maintenance of plumbing, steam, and electrical equipment and/or systems in
accordance with all applicable codes and ordinances.
• Turn off steam supply before installing or servicing.
• Open supply valves slowly to prevent water hammer or sudden shock.
• Wear heat resistant gloves before adjusting steam valves.
• Handle regulator with extreme caution. Do not lift regulator by any external tubing.
Failure to follow this warning may result in property damage, serious burns, personal injury
or death.
W
ARNING
CAUTION
!
WARNING
Series SPS Spring Pilots
For Series 2000 Pilot-Operated
Regulators
Series SPS Spring Pilots
The Series SPS Spring Pilot Control Valve senses and balances
downstream pressure against an adjustable spring to control a
Series 2000 Pilot Operated Regulator main valve and thus regu-
late downstream pressure to a set point. The Series 2000
Regulator reduces a steady or varying inlet pressure to a con-
stant, adjustable delivery pressure.
The Series SPS pilots are spring loaded. Normal accuracy of
regulation is within 10% of set point. The adjustable range of the
delivery pressure is governed by the choice of adjusting spring
as shown below.
Pressure Wire
Range Spring Diameter
psig (bar) Color in. (mm)
2-30 (0.1-2.0) Blue
3
⁄16 (4)
5-60 (0.3-4.1) Red
1
⁄4 (6)
20-175 (1.4-11.9) Gold
11
⁄32 (9)
Hoffman Specialty
Installation & Maintenance
Instructions
HS-621(A)