 Required owing water pressure to the dishmachine is 15-65 PSIG. If pressures 
higher than 65 PSIG are present, a pressure regulating valve must be installed in the water line to the 
dishmachine (by others).
Pressure guage not provided on pumped rinse machines.
Important: The chemical containers should be placed no higher than 10" above oor.
If chemical containers are to be placed in cabinet adjacent to machine, a 1/2" dia. hole is required in 
the cabinet to run chemical supply line.
NOTES:
1.  All vertical machine dimensions taken from oor may be increased by 1".
2.  Moist air escapes from the door.
  Use only moisture resistant materials adjacent to dishmachine sides and top.
3.  A vent hood is not recommended above the undercounter dishmachine since it does not produce 
excessive vapors.
PLUMBING NOTES:
1. Water hammer arrestor (meeting ASSE-1010 standard or equivalent) to be supplied (by others) in 
common water supply line at service connection.
2.  Recommended water hardness to be 3 grains or less for best results.
3. If drain hose is looped above a sink, the loop must not exceed 38" AFF.
CONNECTION INFORMATION
(AFF = ABOVE FINISHED FLOOR)
LEGEND
E1  ELECTRICAL CONNECTION: 1-3/8" DIA. HOLE  
FOR 1" TRADE SIZE CONDUIT; 4-5/8" AFF.
P1  SINGLE FILL AND RINSE CONNECTION:
  3/4" FEMALE GARDEN HOSE FITTING ON 6' LONG 
HOSE SUPPLIED WITH MACHINE; 
  110°F WATER MIN. FOR LXeH.
P2  DRAIN CONNECTION: 5/8" BARB FITTING WITH
  6' LONG HOSE SUPPLIED WITH MACHINE.
MODEL VOLTS/HERTZ/PHASE
RATED 
AMPS
MIN SUPPLY 
CKT CONDUCT 
AMPACITY
MAX 
PROTECTIVE 
DEVICES
LXeH
208-240/60/1 30.5 40 40
120/208-240(3W)/60/1* 30.5 40 40
208-240/60/3 23.9 30 30
220-240/50/1 30.5 40 40
HEAT OUTPUT, BTU/HR
MODEL LATENT SENSIBLE
LXeH 4600 4000
SHIPPING WEIGHTS LXeH
NET WEIGHT OF MACHINE 150 LBS
DOMESTIC SHIPPING WEIGHT 170 LBS
* THIS SYSTEM REQUIRES THREE POWER WIRES WHICH INCLUDES
  A CURRENT CARRYING NEUTRAL, AN ADDITIONAL FOURTH WIRE
  MUST BE PROVIDED FOR MACHINE GROUND.
 ACCESSORY CORD KITS AVAILABLE FOR ALL MACHINES
  NOTE: FOR SUPPLY CONNECTIONS, USE COPPER WIRE ONLY 
RATED AT 90°C MINIMUM.
 Electrical and grounding 
connections must comply with the applicable portions of 
the National Electrical Code and/or other local electrical 
codes.
Plumbing connections must comply with applicable 
sanitary, safety and plumbing codes. Drain and ll line 
congurations vary, some methods are shown on this 
drawing.
INSTALLATION DIAGRAM (LXeH) 
E1 P2 P1
P2
WALL
MIN.
 9"
9 7/16"
3
 RECOMMENDED WATER
 SERVICE ROUGH-IN
 1/2" TRADE SIZE
 PIPE MIN. W/SHUTOFF
 VALVE, LINE STRAINER
 & 3/4" MALE GARDEN
 HOSE FITTING (BY
 CUSTOMER).
1-1/2" TRADE SIZE 
PIPE MIN. REDUCED
DOWN TO 3/4" FPT
CONNECTION (BY
CUSTOMER)
DETERGENT &
RINSE-AID
ADDITIONAL CLEARANCE REQUIRED TO
SLIDE UNIT FORWARD FOR SERVICE ONLY
 CHEMICAL BOTTLES
 MAY BE LOCATED ON
 EITHER SIDE OF MACHINE
E1
FLOOR LINE
P2
TRIM STRIP
(OPTIONAL)
17" OR LESS
RECOMMENDED
 39 1/2"
32 15/16"
CLEARANCE
 SERVICE
 MIN.
32 1/2"
 13/16"
22 5/16"
23 15/16"
43 1/2"
10 9/16"
LOADING
1 1/16"
 HEIGHT
 MAX.
 17"
21"
25 9/16"