HG SERIES GAS FRYERS WITH OR WITHOUT FILTER-IN-A-DRAWER Instructions Manual MODELS HGFS25 ML-126410 HGS35F ML-126952 HGFS35 ML-126411 HGS45F ML-126955 HGFS45 ML-126412 HGS65F ML-126958 HGFS65 ML-126413 HGS85F ML-126961 HGFS85 ML-126414 HGD35F ML-126953 HGFD25 ML-126415 HGD45F ML-126956 HGFD35 ML-126416 HGD65F ML-126959 HGFD45 ML-126417 HGD85F ML-126962 HGFD65 ML-126418 HGC35F ML-126954 HGFD85 ML-126419 HGC45F ML-126957 HGFC35 ML-126420 HGC65F ML-126960 HGFC45 ML-126421 HGC85F ML-126963 HGFC65 ML-126
– 9 –
LOCATION
The equipment area must be kept free and clear of combustible substances. Minimum clearance from
combustible construction is 6" (15 cm) from the sides and 6" (15 cm) from the back of the fryer. Minimum
clearance from noncombustible construction is 0" from the sides and 0" from the back.
At least 16" (41 cm) clearance must be between the fryer and any open-top flame units. Adequate
clearances for servicing and proper operation must be allowed. The unit may be installed on
combustible floors.
Install the fryer in an area with sufficient air supply for combustion of the gas at the fryer burners.
Provide adequate clearance for air openings into the combustion chamber. Do not obstruct the flow of
combustion and ventilation air. Do not permit fans to blow directly on the fryer. Avoid wall-type fans
which create cross-currents within a room. Avoid open windows next to the sides or back.
INSTALLATION CODES AND STANDARDS
The fryer must be installed in accordance with:
In the United States of America:
1. State and local codes.
2. National Fuel Gas Code, ANSI-Z223.1 (latest edition). Copies may be obtained from The
American Gas Association, Inc., 1515 Wilson Blvd., Arlington, VA 22209.
In Canada:
1. Local codes.
2. CAN/CGA-B149.1 Natural Gas Installation Code (latest edition).
3. CAN/CGA-B149.2 Propane Installation Code (latest edition), available from the Canadian Gas
Association, 178 Rexdale Blvd., Etobicoke, Ontario, Canada M9W 1R3.