HG SERIES GAS FRYERS WITH OR WITHOUT FILTER-IN-A-DRAWER Instructions Manual MODELS HGFS25 ML-126410 HGS35F ML-126952 HGFS35 ML-126411 HGS45F ML-126955 HGFS45 ML-126412 HGS65F ML-126958 HGFS65 ML-126413 HGS85F ML-126961 HGFS85 ML-126414 HGD35F ML-126953 HGFD25 ML-126415 HGD45F ML-126956 HGFD35 ML-126416 HGD65F ML-126959 HGFD45 ML-126417 HGD85F ML-126962 HGFD65 ML-126418 HGC35F ML-126954 HGFD85 ML-126419 HGC45F ML-126957 HGFC35 ML-126420 HGC65F ML-126960 HGFC45 ML-126421 HGC85F ML-126963 HGFC65 ML-126

36
FORM 34773 (June 2002) PRINTED IN U.S.A.
ALARMS AND ERROR MESSAGES (HGD and HGC Series)
Pilot Out - If the pilot is out, the control displays the following message:
HGD Series - FIrE OUt
HGC Series - PILOT OUT
If no action is taken after 90 seconds an alarm sounds continuously, the heat demand is disabled and
any running cooking cycles are cancelled. The control displays the following message:
HGD Series - Ign LoC
HGC Series - IGNITION LOCKOUT
The fryer must be turned off, then back on before the pilot can be relit and normal fryer functions
resumed. See pages 14 and/or 15 under Startup for lighting instructions pertaining to your particular
model.
Open Probe - If an open probe is detected, the heat demand is disabled and any running cooking cycles
are cancelled. All operator buttons are disabled. The control displays the following message:
HGD Series - Prob
HGC Series - OPEN PROBE
The alarm sounds continuously until the fault clears or the fryer is turned off then back on. If the problem
persists, call service.
Shorted Probe - If a shorted probe is detected, the heat demand is disabled and any running cooking
cycles are cancelled. All operator buttons are disabled. The control displays the following message:
HGD Series - Hi
HGC Series - SHORTED PROBE
The alarm sounds continuously until the fault clears or the fryer is turned off then back on. If the problem
persists, call service.
Hi Temperature - If the actual temperature is greater or equal to 415°F (212°C), the heat demand is
disabled and any running cooking cycles are cancelled. All operator buttons are disabled. The control
displays the following message:
HGD Series - Hi
HGC Series - SHORTED PROBE
The alarm sounds continuously until the fault clears or the fryer is turned off then back on. Normal fryer
operations resumes when temperature drops below 415°F (212°C). If the problem persists, call
service.