Instruction DISHWASHERSML-38898 ML-38899 ML-104047 ML-104050 C44AW ML-103946 ML-103947 ML-104082 ML-104083 C54A ML-104199 ML-104198 C64A ML-103908 ML-103909 C88A ML-110042 ML-110041 CRS66A ML-38947 ML-38948 ML-104052 ML-104055 CRS66AW ML-103958 ML-103959 ML-104086 ML-104087 CRS76A ML-104202 ML-104201 CRS86A ML-103910 ML-103911 CRS110A ML-110044 ML-110043 CCS66A ML-104321 ML-104320 CCS66AW ML-104323 ML-104322 CCS76A ML-104325 ML-104324 CCS86A ML-104327 ML-104326 CCS110A ML-110046 ML-110045 CPW80A ML-3
– 15 –
If using the 'Pant-Leg' duct, a mini vent hood (Fig. 8), positioned about 18" above the flue exit at the rear
of the dishwasher and connected to existing duct work, must be used for the flue gases. The volume
of flue exhaust in the mini vent hood should not exceed 200 CFM.
Fig. 8
In either case, if a powered means of exhaust is used, an electrical interlock must be provided to allow
the flow of gas to the dishwasher burner only when the exhaust system is in operation.
For additional information, refer to the National Fuel Gas Code, ANSI Z223.1, NFPA 54.
In all cases, local codes will prevail.