DESCRIPTION
The Hubbell Control Solutions NXRM2 radio module allows NX distributed lighting controls to communicate wirelessly with wired and other
wireless components in the NX system.
SPECIFICATIONS
Classication Class 2 Device/Raintight
Electrical Ratings Input: 12-24 VDC
Control Connection Low Voltage SmartPORT™
Operating Environment
Operating Temperature: -40°F to 185°F [-40°C to 85°C]
Relative humidity (non-condensing): 0 to 95%, IP65 Rated
Construction Housing: GSM UL Rated 94 HB Plastic
Mounting Mounts through 1.2” D hole in xture housing
Dimensions
2.1”L x 1.5”D Overall (1.4”L x 1.2”D Stem)
53.34mm L x 38.1mm D Overall (35.56mm L x 30.48mm D Stem)
Weight 4.0 oz (113.4 g)
Color White, Black, or Gray
Patents Patent(s) Pending
Certications cULus listed, FCC Part 15.247, Conforms with UL916 and certied to CAN/CSA C22.2
Warranty Five-year limited
NXRM2-H INSTALLATION
The NXRM2 radio module is a self-contained assembly which includes the RF radio, Bluetooth® radio, control electronics, and antenna. A
threaded stem and lock nut are provided for mounting through a 1.2” aperture and xture housing. Located on the back of the unit, a pair (2) of
miniature SmartPORT™ connectors are used for connection to an NXFM xture module or other NX smart components.
1. Remove the lock nut from the threaded stem of the unit.
2. Insert the stem through the opening in the housing. See gure 1.
3. Carefully snug (do not overtighten) the nut against the housing making sure the gasket is pulled up tight against the housing. See gure 2.
4. Use the appropriate Hubbell manufactured cable to connect the radio module to the NXFM xture module. The second connector is
provided to allow a series connection with other NX modules.