Step 4: Outputs
2) Choose Outputs.
1) Press to enter the sengs menu.
OK
The device includes four freely congurable outputs. Current
(oponal) or voltage output can be chosen for each of them.
The output signal has to be chosen rst with a jumper (see the
installaon instrucons), aer which the output sengs can be
changed in the Outputs menu.
OK
+
–
Settings
Brightness
Modbus
Outputs
Measurement: Not in use / Celsius
1*
/ Fahrenheit
1*
/ CO2 /
Humidity / TVOC ppm
2*
/ CO2 EQ /
TVOC ug/m3
2*
/ PM2.5 hour / PM10 hour /
PM2.5 day / PM10 day / PM1 / PM2.5 /
PM10
1*) Only one of these can be chosen for outputs.
2*) Only one of these can be chosen for outputs.
OK
+
–
Outputs
Out1 Celsius
Out2 Humidity
Out3 Not in use
OK
+
–
Not in use
CO2
TVOC ppm
CO2 EQ
Scale: 0–10 V / 2–10 V / 0–5 V
1*
/ 4–20 mA
2*
1*) When using voltage output, the jumper
seng of that output must be set to V.
2*) When using current output, the jumper
seng of that output must be set to mA.
High limit: See Table 1 - Output limits
Low limit: See Table 1 - Output limits
OK
+
–
Output scale
0-10V
2-10V
0-5V
OK
+
–
Low limit
CO2
400
OK
+
–
High limit
CO2
2000
Figure 4a
Figure 4b
3) Choose measurement, scale and limits for each output.
• The menus and limits can be scrolled by pressing the
and buons. Choose the measurement and scale
and set the limits by pressing the buon.
+
–
OK