Instruction Manual

Copyright HK Instruments 2021 www.hkinstruments. Installaonversion7.02021
INSTALLATION
INSTRUCTIONS
HUMIDITY TRANSMITTERS
RHT-MOD Series
READ THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS
DEVICE.
• Failuretoobservesafetyinformaonandcomplywith
instruconscanresultinPERSONALINJURY,DEATHAND/OR
PROPERTY DAMAGE.
• Toavoidelectricalshockordamagetoequipment,disconnect
powerbeforeinstallingorservicinganduseonlywiringwith
insulaonratedforfulldeviceoperangvoltage.
• Toavoidpotenalreand/orexplosiondonotuseinpotenally
ammableorexplosiveatmospheres.
• Retaintheseinstruconsforfuturereference.
• Thisproduct,wheninstalled,willbepartofanengineered
systemwhosespecicaonsandperformancecharacteriscs
arenotdesignedorcontrolledbyHKInstruments.Review
applicaonsandnaonalandlocalcodestoassurethatthe
installaonwillbefunconalandsafe.Useonlyexperiencedand
knowledgeabletechnicianstoinstallthisdevice.
SPECIFICATIONS
Thank you for choosing an HK Instruments RHT-MOD series rela-
vehumiditytransmier.TheRHT-MODseriesisintendedforusein
commercialenvironmentsinHVAC/Rapplicaons.
TheRHT-MODmeasuresrelavehumidity(rH),andtemperature(T).
RHT-MODdevicesareavailablewithlargetouchscreendisplaymak-
ingconguraonofthedevicequickandeasy.
RHT-MODseriesdevicesarecommonlyusedtomonitor:
•humidityandtemperaturelevelsinoces,publicspaces,hospitals,
meengroomsandclassrooms
•humidityandtemperatureinvariouscommercialapplicaons
•humidityandtemperatureinHVAC/Renvironment
SPECIFICATIONS
Performance
Measurement ranges:
Temperature:0...50°C
Relavehumidity:0–100%
Accuracy:
Temperature:<0.5ºC
Relavehumidity:±2...3%at0...50°Cand10–90%rH
Totalerrorbandincludesaccuracy,hysteresisand
temperatureeectover5...50°Cand10–90%rH.
Technical Specicaons
Media compability:
Dryairornon-aggressivegases
Measuring units:
°Cand%rH
Measuring element:
Temperature:Integrated
Relavehumidity:Thermosetpolymercapacive
sensingelement
Environment:
Operangtemperature:0...50°C
Storagetemperature:-20...70°C
Humidity:0to95%rH,noncondensing
Physical
Dimensions:
Case:99x90x32mm
Weight:
150g
Mounng:
3screwholessloed,3.8mm
Materials:
Case:ABS
Protecon standard:
IP20
Display
Touchscreen
Size:77.4x52.4mm
Electrical connecons:
Powersupply:
5-screwterminalblock
(24V,GND)
0.21.5mm
2
(12–24AWG)
Relayout:
3-screwterminalblock
(NC,COM,NO)
0.21.5mm
2
(12–24AWG)
Electrical
Input: 24VACorVDC,±10%
Currentconsumpon:max90mA(at24V)+
10mAforeachvoltageoutputor20mAfor
eachcurrentoutput
Relayout:
SPDTRelay,250VAC/30VDC/6A
Adjustableswitchingpointandhysteresis
Oneanalogoutputforselectedmedia:
0/2*10VDC,LoadRminimum1kΩ
*(2–10VDCdisplaymodelsonly)or
4–20mA,maximumload500Ω
Communicaon
Protocol:MODBUSoverSerialLine
TransmissionMode:RTU
Interface:RS485
Byteformat(11bits)inRTUmode:
CodingSystem:8-bitbinary
BitsperByte:
1startbit
8databits,leastsignicantbitsent
rst
1bitforparity
1stopbit
Baudrate:selectableinconguraon
Modbusaddress:1−247addressesselectablein
conguraonmenu
Conformance
MeetsrequirementsforCEmarking:
EMCDirecve2014/30/EU
RoHSDirecve2002/95/EC
LVDDirecve2014/35/EU
WEEEDirecve2012/19/EU
INTRODUCTION WARNING
APPLICATIONS
COMPANY WITH
MANAGEMENT SYSTEM
CERTIFIED BY DNV GL
= ISO 9001 = ISO 14001 =
RoHS 2
2011/65/EU

Summary of content (4 pages)