Instruction Manual
Copyright HK Instruments 2023 www.hkinstruments.
Installaonversion4.02023
INSTALLATION
INSTRUCTIONS
Measurement probe
Floxact
TM
• READ THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS
DEVICE.
• Failuretoobservesafetyinformaonandcomplywith
instruconscanresultinPERSONALINJURY,DEATHAND/OR
PROPERTY DAMAGE.
• Toavoidelectricalshockordamagetoequipment,disconnect
powerbeforeinstallingorservicinganduseonlywiringwith
insulaonratedforfulldeviceoperangvoltage.
• Toavoidpotenalreand/orexplosiondonotuseinpotenally
ammableorexplosiveatmospheres.
• Retaintheseinstruconsforfuturereference.
• Thisproduct,wheninstalled,willbepartofanengineered
systemwhosespecicaonsandperformancecharacteriscs
arenotdesignedorcontrolledbyHKInstruments.Review
applicaonsandnaonalandlocalcodestoassurethatthe
installaonwillbefunconalandsafe.Useonlyexperiencedand
knowledgeabletechnicianstoinstallthisdevice.
To measureair ow accurately in avenlaonduct, use a special
FloXact™measurementprobetogetherwithaDPT-Flowtransmit-
ter.
TherearetwoFloXact™modelsavailable:RmodelforroundductsandLforrectangularducts.Inordertoachievethebestaccuracy,itis
recommendedtousetwoFloXact™-Lprobesiftheheightofarectangularductismorethan350mm,threeprobesiftheductsizeis700mmor
more,andfourprobesiftheductsizeis1000mmormore.
FloXact™-R modelsavailable:100,125,160,200,250,315,400and450andallotherstandardroundductsizesupto1200mm.
FloXact™-L modelsavailable:250,300…1200(50mmsteps)
Lengthoftheprobe(L)isdenedbythewidth(W)oftheduct.(Seestep5).
Othersizesareavailableonrequest.
Example:
fora160mmroundduct,chooseFloXact-R160probe,andfora500x400mmrectangularduct,choosetwoFloXact-L500probes.
step 2: SELECTING THE CORRECT DPT-FLOW MODEL
INTRODUCTION
STEp 1: SELECTING THE CORRECT FLOXACT
TM
PROBE
WARNING
ItisrecommendedtouseDPT-Flow-1000-AZ-DmodelwithFloXact
TM
probesbecausedynamicductpressureisrarelyover500Pa.Typical
pressurerangeinavenlaonductis0…250Pa.
ThemeasurementrangeofDPT-Flow-1000-AZ-Dis0...1000Pa.