Datasheet

Keihästie 7, 40950 Muurame,
Finland
Phone: +358 14 337 2000
Fax: +358 14 337 2020
Email: info@hkinstruments.fi
www.hkinstruments.fi
Electrical Connection:
0-10V Output 0…10 V
4-20mA Output 4…20 mA
24V Supply 24 VAC or VDC
GND Ground
Dimensions
Installation
0-10V
4-20mA
24V
GND
V
A
24VDC / 24VAC
+
Output 4...20mA
Output 0...10V
Power supply
Jumper 1
Jumper 2
Jumper 3
Jumper 4
Jumper 5
Jumper 6
Jumper 4
0.8 s
4.0 s
Jumper 5
Jumper 6
Select unit
Not in use
Note: Measuring unit
can be change
pressing button when
Jumper 5 is placed.
Please remove
jumper after setting.
Set response time
1000Pa 1500Pa 2000Pa 2500Pa
Jumper 1
Jumper 2
Jumper 3
Jumper 1
Jumper 2
Jumper 3
±100Pa 100Pa 250Pa 500Pa
Model DPT2500
Jumper 1
Jumper 2
Jumper 3
Jumper 1
Jumper 2
Jumper 3
1000Pa 1500Pa 2000Pa 2500Pa
3000Pa 4000Pa 5000Pa 7000Pa
Model DPT7000
LED: Turns ON
Zeroing
ZEROING: Press the button