Instruction Manual

Copyright HK Instruments 2022 www.hkinstruments. Installaonversion8.02022
7)Selecttheresponseme:1...20s.
RESPONSETIME
4 s
SELECT
UP
DOWN
BAUD RATE
9600
SELECT
UP
DOWN
PARITY BIT
NONE
SELECT
UP
DOWN
5)Selectthebaudrate:9600/19200/38400.
6)Selecttheparitybit:None/Even/Odd
9)Selecttheinputtype.
Passivetemperaturesensors:PT1000/Ni1000/Ni1000LG/NTC10k
Voltageinput:VINPUT
Switchinput:BININ
Noinput:NONE
INPUT
PT1000
SELECT
UP
DOWN
10)Selectthesetpointofthecontroller(SP2isonlyavailablewithBININswitch
informaon):
CONFIGURATION CONTINUED
NOTE! Always zero the device before use.
Supplyvoltagemustbeconnectedonehourbeforethezeropointadjust-
mentiscarriedout.AccessviaModbusorbypushbuon.
1)Loosebothtubesfromthepressureinlets+and-.
2)Acvatethedevicemenubypushingthetheselectbuonfor2
seconds.
3)SelectZero sensorbypressingtheselectbuon.
4)WaitunltheLEDturnsoandtheninstalltubesagainforthe
pressureinlets.
STEP 4: ZERO POINT ADJUSTMENT
SELECT
STEP 5: INPUT SIGNAL CONFIGURATION
InputsignalscanbereadoverModbusviaDPT-MODRS485interface.
Signals Accuracy for measurement Resoluon
0...10V <0,5% 0,1%
NTC10k <0,5% 0,1%
Pt1000 <0,5% 0,1%
Ni1000/(-LG) <0,5% 0,1%
BININ(potenalfreecontact)
Thejumpersshould be set accordingtothe instruconsbelowandthe value
shouldbereadfromtherightregister.
Figure 3 - Input signal conguraon
J1
J2
J3
IN
J1
J1
J1
J2
J2
J2
J3
J3
J3
NTC10k / BIN IN
Pt1000 / Ni1000/(-LG)
0...10 V
D-VALUE
1.00
SELECT
UP
DOWN
15)Pushtheselectbuontoexitmenu.
SELECT
EXIT MENU
SELECT
12)Selectproporonalbandaccordingtoyourapplicaon
specicaons.
P-VALUE
206
SELECT
UP
DOWN
13)Selectintegralgainaccordingtoyourapplicaonspecicaons.
I-VALUE
4.00
SELECT
UP
DOWN
14)Selectderivaonmeaccordingtoyourapplicaon
specicaons.
STEP 6: TEMPERATURE COMPENSATION
Thedeviceincludesanoutdoortemperaturecompensaonfunconthatcan
beenabledfromthemenu.Whenacvatedandanoutdoortemperaturesensor
isaached,theeecvesetpointofthedevicewillbemodiedtocompensate
forthecoldoutdoorair.Thismayresultinenergysavings.
If temperaturecompensaonis enabled, thedevicewill linearly decreasethe
user’s setpoint (REF FLOW/REF PRESSURE) by 0 % to TC DROP % from TC
START TE to TC STOP TE.
Thedeviceenforcesa+5°Cdierence betweenthe startand stoptempera-
tures.Thestarttemperaturemustbehigherthanthestoptemperature.
1)Connectandcongureanoutdoorairtemperaturesensor.Seestep5.
2)Enabletemperaturecompensaon.
4)Setthestoppingtemperatureforcompensaon.
TC STOP TE
-15 °C
SELECT
UP
DOWN
TEMP COMP
ON
SELECT
UP
DOWN
TC START TE
5 °C
SELECT
UP
DOWN
3)Setthestarngtemperatureforcompensaon.
5)Setthemaximumdroppercentageforcompensaon.
TC DROP %
25.0
SELECT
UP
DOWN
8)SelecttheFixedOutput(OFF/0...100%),(seestep7FixedOutput).
10.1)IftheCONTROLUNITisselectedPRESSURE.
SELECT
UP
DOWN
REF PRES SP1
10 Pa
REF PRES SP2
100 Pa
10.2)IftheCONTROLUNITisselectedFLOW.
SELECT
UP
DOWN
REF FLOW SP1
25.000 m3/s
REF FLOW SP2
35.000 m3/s
11)SelecttheTEMPCOMP(OFF/ON),(seestep6,TemperatureCompensaon).