Instruction Manual

Copyright HK Instruments 2021 www.hkinstruments. Installaonversion7.02021
CAUTION!
•ForCEcompliance,aproperlygroundedshieldingcableis
required.
•Usecopperwireonly.Insulateorwirenutallunusedleads.
•Supplyaseparatecableforrelayandsignaloutwhenusingline
voltagetopowertherelay.
•Anywiringmaycarrythefulloperanglinevoltagecurrentbased
oneldinstallaon.Thecoverlockingscrewmustbeinstalledif
thelinevoltageissuppliedtotherelay.
•Careshouldbeusedtoavoidelectrostacdischargetothedevice.
•Thisunithasconguraonjumpers.Youmayneedtorecongure
thisdeviceforyourapplicaon.
1)Routethecablesthroughthesquareopeninginthebackplateor
forsurfacewiringselectaknockoutonthetoporboomofthe
wallplate,asshowninFigure2a.
2)ConnectthewiresasshowninFigure2band2c.
WIRING DIAGRAMS CONTINUED
Figure 2a - Roung the cables
24 V
GND
CO
2
rH
Temp
+
Output 0/2–10 V / 4–20 mA
Output 0/2–10 V / 4–20 mA
Output 0/2–10 V / 4–20 mA
Figure 2b - Wiring diagram: Power input & signal output
Wires can be routed through the square opening in the back plate
Wires can be routed through the top knockouts
Wirescanberoutedthroughtheboomknockouts
Figure 2d - Wiring diagram: Relay
NC
COM
NO
STEP 2: WIRING DIAGRAMS
NOTE!Whenusinglongconneconwiresitmaybenecessarytousea
separateGNDwireforvoltageoutputcurrenttopreventmeasurement
distoron.TheneedforanextraGNDwiredependsonthecrosssec-
onandlengthoftheusedconneconwires.Iflongand/orsmallcross
seconwiresareused,supplycurrentandwireresistancemaygener-
ate avoltage drop in the common GNDwire resulng in adistorted
outputmeasurement.
24 V
GND
CO
2
rH
+
Temp
V V V
Output 0/2...10 V
Output 0/2...10 V
Output 0/2...10 V
Figure 2c - Wiring diagram: Extra GND wire
STEP 3: CONFIGURATION
ConguraonoftheCDTseriesdeviceconsistsof:
1)Conguringthejumpers(seestep4).
2)Conguraonmenuopons.
(Display-andModbusversionsonly.Seetheusermanualfor
furtherdetails.)