Instruction Manual

Copyright HK Instruments 2022 www.hkinstruments. Installaon version 7.0 2022
INSTALLATION
INSTRUCTIONS
AIR FLOW AND VELOCITY TRANSMITTERS
AVT Series
Thank you for choosing an HK Instruments AVT series air velocity
transmier. The AVT series is intended for use in commercial environ-
ments. It is designed with a duct mount probe and adjustable collar
suitable for round or rectangular ducts. The AVT series provides sepa-
rate readings for air velocity and temperature.
The AVT series comes with three measurement ranges in a single de-
vice (02 m/s, 010 m/s, 020 m/s). The AVT series is available with
oponal display and relay.
READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING
TO INSTALL, OPERATE OR SERVICE THIS DEVICE.
Failure to observe safety informaon and comply with instrucons
can result in PERSONAL INJURY, DEATH AND/OR PROPERTY
DAMAGE.
To avoid electrical shock or damage to equipment, disconnect
power before installing or servicing and use only wiring with
insulaon rated for full device operang voltage.
To avoid potenal re and/or explosion do not use in potenally
ammable or explosive atmospheres.
Retain these instrucons for future reference.
This product, when installed, will be part of an engineered system
whose specicaons and performance characteriscs are not
designed or controlled by HK Instruments. Review applicaons
and naonal and local codes to assure that the installaon will
be funconal and safe. Use only experienced and knowledgeable
technicians to install this device.
• Fuse at load supply (normally 6 A, 10 A, 16 A) does not always limit
the relay output load current to 6 A. Relay Maximum Load (250 V x
6 A res.)
• Add an external fuse to relay common connector. Use a me-lag
fuse (max 6 A) that is in accordance with the standard IEC 60127-2.
The product doesn’t have an internal fuse for the relay.
CAUTION: The product may only be connected to overvoltage
category II electricity network according to IEC 60664-1.
Performance
Measurement ranges:
Velocity:
Range: 0–2 m/s
Range: 0–10 m/s
Range: 0–20 m/s
Temperature: 0−50 °C
Accuracy:
Velocity:
Range: 0...2 m/s: <0.2 m/s + 5 % from reading
Range: 0...10 m/s: <0.5 m/s + 5 % from reading
Range: 0...20 m/s: <1.0 m/s + 5 % from reading
Thermal shi: ±0.8 % FS / °C
Units calibrated at 22 °C. Rapid thermal shi
stabilisaon me 10 min.
Temperature: <0.5 ºC typical @25ºC (velocity > 0.5 m/s)
Technical Specicaons
Media compability:
Dry air or non-aggressive gases
Measuring units:
m/s and °C
Measuring element:
Temperature: ntc10k
Velocity: Pt1000
Environment:
Operang temperature: 0...50 °C
Storage temperature: -20...70 °C
Humidity: 0 to 95 % rH, non-condensing
Physical
Dimensions:
Case : 86.0 x 95.0 x 36.0 mm
Probe: OD 10 mm, length 210 mm from boom of the
cover
Immersion Length with Flange: Adjustable 50180 mm
Weight:
220 g
Mounng:
Mounng ange, ø 4.0 mm
Materials:
Case: ABS
Lid: PC
Probe: Stainless steel 304
Mounng ange: LLPDP
Protecon standard:
IP54
Display
3 1/2 digit LCD backlit display
Size: 45.7 x 12.7 mm
Electrical connecons:
Power supply & signal out: 4-screw terminal block
16–24 AWG (0.21.5 mm
2
)
Relay Out: 3-screw terminal block
16-24 AWG (0.2–1.5 mm
2
)
Cable entry:
M16
Electrical
Input: 24 VDC / 24 VAC ± 10 %
Current consumpon 35 mA (50 mA with relay)
+ 40 mA with mA-outs
Output signal 1: (T out)
0–10 V (linear to temperature)
L min 1 kΩ
4–20 mA (linear to temperature)
L max 400 Ω
Output signal 2: (v out)
0–10 V (linear to m/s)
L min 1 kΩ
4–20 mA (linear to m/s)
L max 400 Ω
Relay Out: 3-screw terminal block
(NC, COM, NO)
Potenal free SPDT
250 VAC, 6A / 30 VDC, 6 A adjustable switching point
and hysteresis
Conformance
Meets the requirements for:
CE: UKCA:
EMC: 2014/30/EU S.I. 2016/1091
RoHS: 2011/65/EU S.I. 2012/3032
LVD/EESR: 2014/35/EU S.I. 2016/1101
WEEE: 2012/19/EU S.I. 2013/3113
SPECIFICATIONS
INTRODUCTION
AVT series devices are commonly used in HVAC/R systems for:
• in-duct air ow and velocity monitoring
• in-duct temperature monitoring
• VAV applicaons
APPLICATIONS
WARNING
RoHS
COMPLIANT