User's Manual
Using the Front Panel Keypad
Inverter Mounting
and Installation
2–26
Selecting 
Functions and 
Editing Parame-
ters
In order to run the motor for the powerup test, this section will show how to:
• select the inverter’s maximum output frequency to the motor
• select the keypad potentiometer as the source of motor speed command
• select the keypad as the source of the RUN command
• set the number of poles for the motor
• enable the RUN command
The following series of programming tables are designed for successive use. Each table uses 
the previous table’s final state as the starting point. Therefore, start with the first and continue 
programming until the last one. If you get lost or concerned that some of the other parameters 
settings may be incorrect, refer to “
Restoring Factory Default Settings” on page 6–9.
CAUTION: If you operate a motor at a frequency higher than the inverter standard default 
setting (50Hz/60Hz), be sure to check the motor and machine specifications with the respective 
manufacturer. Only operate the motor at elevated frequencies after getting their approval. 
Otherwise, there is the danger of equipment damage.
Setting the Motor Base Frequency -The motor is designed to operate at a specific AC 
frequency. Most commercial motors are designed for 50/60 Hz operation. First, check the 
motor specifications. Then follow the steps in the table below to verify the setting or correct for 
your motor. DO NOT set it for greater than 50/60 Hz unless the motor manufacturer specifi-
cally approves operation at the higher frequency. 
TIP: If you need to scroll through a function or parameter list, press and hold the   or   
key to auto-increment through the list.
Action Display Func./Parameter
Press the 
 key.
Monitor functions
Press the   or   keys until ->
“A” Group selected
Press the   key.
First “A” parameter
Press the   key twice.
Base frequency setting
 Press the   key.
or
Default value for base frequency 
US = 60 Hz, Europe = 50 Hz
Press the   or   key as needed.
Set to your motor specs (your 
display may be different)
Press the   key.
Stores parameter, returns to “A” 
Group list
FUNC
d 001
1
2
A–––
FUNC
A001
1
A003
FUNC
60
50
1
2
60
STR
A003
1
2