B–15
Command – 08 The 08 command initializes the inverter parameters to the factory default values. First, you 
must set B84 (use command 07) to specify whether you want to clear the trip history at the 
same time. Also, set B85 to specify the country code for the initialization (use command 07).
The frame format of command 08 follows the 
diagram and specification table.
Command – 09 The 09 command verifies whether or not it is 
possible to set a particular parameter in the 
EEPROM. The frame format of command 08 
follows the diagram and specification table.
The receive frame includes an ACK 
(acknowledge) character, followed by a
2-byte data field with the result.
Element Description Size Valu e
STX Control code (STart of TeXt) 1 byte STX (0x02)
Node Node (station) address of inverter 2 bytes 01 to 32, and FF (broadcast to all 
nodes)
Command Transmission command 2 bytes 08
BCC Block check sum code 2 bytes Exclusive OR of Node, 
Command, and Data
[CR] Control code (carriage return) 1 byte [CR] (0x0D)
STX Node Command BCC [CR]
Frame format
Element Description Size Valu e
STX Control code (STart of TeXt) 1 byte STX (0x02)
Node Node (station) address of inverter 2 bytes 01 to 32
Command Transmission command 2 bytes 09
BCC Block check sum code 2 bytes Exclusive OR of Node, 
Command, and Data
[CR] Control code (carriage return) 1 byte [CR] (0x0D)
Element Description Size Valu e
STX Control code (STart of TeXt) 1 byte STX (0x02)
Node Node (station) address of inverter 2 bytes 01 to 32
ACK Control code (ACKnowledge) 1 byte ACK (0x06)
Data Parameter value 2 bytes 00 = setting not allowed,
01 = setting is allowed
BCC Block check sum code 2 bytes Exclusive OR of Node, 
Command, and Data
[CR] Control code (carriage return) 1 byte [CR] (0x0D)
STX Node Command BCC [CR]
Transmit frame format
STX
Node ACK Data BCC [CR]
Receive frame format