“C” Group: Intelligent Terminal Functions
Configuring Drive 
Parameters
3–60
Analog Signal 
Calibration 
Settings
The functions in the following table configure the signals for the analog output terminals. Note 
that these settings do not change the current/voltage or sink/source characteristics – only the 
zero and span (scaling) of the signals.
NOTE: Settings C081, C082, C083, C121, C122, C123 are factory-calibrated for each inverter. 
Do not change these settings unless absolutely necessary. Note that if you restore factory 
defaults for all parameters, these settings will not change.
“C” Function
Run 
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
C081 [O] input span calibra-
tion
Range is 0 to 65530 ✔ ✔ Factory-calibrated —
>C081 O-ADJUST
TOP  02119
C082 [OI] input span calibra-
tion
Range is 0 to 65530 ✔ ✔ Factory-calibrated —
>C082 OI-ADJUST
TOP  02512
C083 [O2] input span calibra-
tion
Range is 0 to 65530 ✔ ✔ Factory-calibrated —
>C083 O2-ADJUST
TOP  02818
C085 Thermistor input tuning Range is 0.0 to 1000 ✔ ✔
105.0 105.0 105.0
—
>C085 THERM
ADJUST 0105.0
C086 [AM] terminal offset 
tuning
Range is 0.0 to 10.0V ✔ ✔ 0.0 0.0 0.0 V
>C086 AM-MONITOR
OFFSET  00.0V
C087 [AMI] terminal meter 
tuning
Range is 0.0 to 250% ✔ ✔ 80. 80. 80. %
>C087 AMI-MON
ADJUST  080
C088 [AMI] terminal offset 
tuning
Range is 0 to 20mA ✔ ✔ Factory-calibrated mA
>C088 AMI-MON
OFFSET 04.0mA
C121 [O] input zero calibra-
tion
Range is 0 to 6553 (65530) ✔ ✔ Factory-calibrated —
>C121 O-ADJUST
ZERO  00000
C122 [OI] input zero calibra-
tion
Range is 0 to 6553 (65530) ✔ ✔ Factory-calibrated —
>C122 OI-ADJUST
ZERO  00000
C123 [O2] input zero calibra-
tion
Range is 0 to 6553 (65530) ✔ ✔ Factory-calibrated —
>C123 O2-ADJUST
ZERO  03622