Technical Information
Capacities and selection data
TCGB0079 rev.0 - 01/2013
70
4.5 Correction curve factor
4.5.1 Cooling
The curves are based on High speed of indoor fan. To calculate the cooling capacity of medium or low speed of indoor fan,
multiply cooling capacity of high speed by correction curve factor.
Outdoor Unit HP
Indoor Unit fan speed 2 - 6 8 10/12
High 1.00 1.00 1.00
Medium 0.98 0.94 0.94
Low 0.95 0.86 0.87
4.5.2 Heating
The curves are based on High speed of indoor fan. to calculate the cooling capacity of medium or low speed of indoor fan,
multiply cooling capacity of high speed by correction curve factor.
The curve does not include decreasing capacity by defrosting operation.
Outdoor Unit HP
Indoor Unit fan speed 2 - 6 8 10/12
High 1.00 1.00 1.00
Medium 0.98 0.86 0.86
Low 0.97 0.77 0.76
TCGB0079_rev0_11-2012.indb 70 29/01/2013 14:27:06