Technical Information

General data
Component data
TCGB0079 rev.0 - 01/2013
46
RAS-(8-12)HNC(E)
MODEL RAS-8HNCE RAS-10HNCE RAS-12HNC
Heat exchanger
Type Multi-pass cross-nned tube
Pipe material Copper
Outer diameter mm 7
Rows 3 2
No. of tubes in the Heat exchanger 198 160
Fin material Aluminium
Fin pitch 1.4
Maximum operating pressure MPa 4.15
Total front area m
2
1.35 1.86
No. of Heat exchanger per unit 1
Fan
Fan type Direct drive propeller fan
Fans per unit 2
Outer diameter mm 544
Revolutions rpm 586/717 640/787 630/880
Nominal air ow m
3
/min 127 134 163
Motor
Shell Drip-proof type enclosure
Starting Direct current control
Power W 100 + 100
Quantity 2
Insulation class E
Compressor DA50PHD-D1SE2 DA65PHD-D1SE2
TCGB0079_rev0_11-2012.indb 46 29/01/2013 14:27:00