Technical Information

General data
Component data
TCGB0079 rev.0 - 01/2013
44
3.4 Component data
3.4.1 IVX Premium series
RAS-(2-3)HVNP(E)
MODEL RAS-2HVNP RAS-2.5HVNP RAS-3HVNPE
Heat exchanger
Type Multi-pass cross-nned tube
Pipe material Copper
Outer diameter mm 8 7
Rows 2 2
No. of tubes in the Heat exchanger 44 76
Fin material Aluminium
Fin pitch 1.45 1.4
Maximum operating pressure MPa 4.15
Total front area m
2
0.47 34.9
No. of Heat exchanger per unit 1
Fan
Fan type Direct drive propeller fan
Fans per unit 1
Outer diameter mm 449 544
Revolutions rpm 770 465
Nominal air ow m
3
/min 41 45
Motor
Shell Drip-proof type enclosure
Starting Direct current control
Power W 40 100
Quantity 1 1
Insulation class E E
Compressor EU1114D9 EU140XA2 2YC45KXD
RAS-S(4-6)HVNPE
MODEL RAS-4H(V)NPE RAS-5H(V)NPE RAS-6H(V)NPE
Heat exchanger
Type Multi-pass Cross nned tube
Pipe material Copper
Outer diameter mm 7
Rows 2
No. of tubes in the Heat exchanger 132
Fin material Aluminium
Fin pitch 1.4
Maximum operating pressure MPa 4.15
Total front area m
2
1.35
No. of Heat exchanger per unit 1
Fan
Fan type Direct drive propeller fan
Fans per unit 2
Outer diameter mm 544
Revolutions rpm 459/376 516/422 573/469
Nominal air ow m
3
/min 80 90 100
Motor
Shell Drip-proof type enclosure
Starting Direct current control
Power W 100 + 100
Quantity 2
Insulation class E
Compressor E402HHD-36A2 (1~) / E402HHD-36D2 (3N~)