Technical Information
General data
IVX Premium series
TCGB0079 rev.0 - 01/2013
36
OUTDOOR UNITS RAS-8HNPE RAS-10HNPE RAS-12HNP
Power supply - 3N~ 400V 50Hz 3N~ 400V 50Hz 3N~ 400V 50Hz
Nominal cooling capacity (min-max) kW 20.0 ( 8.0-22.4) 25.0 (10.0-28.0) 30.0 (11.2-33.5)
Nominal heating capacity (min-max) kW 22.4 (6.3-28.0) 28.0 (8.0-35.0) 33.5 (9.0-37.5)
EER (*) 3.56 3.07 2.65
COP (*) 4.21 3.84 3.64
Minimum - Maximum indoor units
connectable
- 1 - 8 1 - 8 1 - 8
Minimum - Maximum connected ca-
pacity
% 50% -120% 50% -120% 50% -120%
Noise level cooling (sound pressure)
(night mode)
dB(A) 57 (55) 58 (56) 59 (57)
Noise level heating (sound pressure) dB(A) 59 60 61
Noise level (sound power) dB(A) 76 76 77
Air ow (cooling / heating) m
3
/min 127 134 163
Dimensions (H x W x D) mm 1380 x 950 x 370 1380 x 950 x 370 1650 x 1100 x 390
Net weight kg 136 138 168
Recommended circuit breaker A 30 30 30
Starting current A
Less than maximum
current
Less than maximum
current
Less than maximum
current
Maximum current A 24.0 24.0 24.3
Running current cooling A 8.6 12.6 17.5
Running current heating A 8.1 11.3 14.2
Power cable size (according to EN
60335-1)
quantity x
mm
2
5 x 6.0 5 x 6.0 5 x 6.0
Transmitting cable size between in-
door unit and outdoor unit
quantity x
mm
2
2 x 0.75 2 x 0.75 2 x 0.75
Piping diameter (liquid / gas) mm (inch) Ø9.52 (3/8) / Ø25.4 Ø12.07 (1/2) / Ø25.4 Ø12.07 (1/2) / Ø25.4
Minimum piping length m 5 5 5
Maximum piping length chargeless m 30 30 30
Maximum piping length (additional
refrigerant charge needed)
m (g/m) 100 (need to be calculate) 100 (need to be calculate)
100 (need to be cal-
culate)
Height difference (O.U. higher / O.U.
lower)
m 30 / 20 30 / 20 30 / 20
Working range (cooling // heating) °C
-5 / +46 (DB) //
-20 / +15(WB)
-5 / +46 (DB) //
-20 / +15(WB)
-5 / +46 (DB) //
-20 / +15(WB)
Refrigerant - R410A R410A R410A
Refrigerant charge before shipment kg 5.7 6.2 6.7
Compressor type - Scroll DC Inverter driven Scroll DC Inverter driven
Scroll DC Inverter
driven
Remote control model (Optinal) PC-ART / PC-ARF PC-ART / PC-ARF PC-ART / PC-ARF
TCGB0079_rev0_11-2012.indb 36 29/01/2013 14:26:59