Technical Information

General data
IVX Premium series
TCGB0079 rev.0 - 01/2013
34
OUTDOOR UNITS RAS-5HVNPE RAS-6HVNPE
Power supply - 1~ 230V 50Hz 1~ 230V 50Hz
Nominal cooling capacity (min-max) kW 12.5 (5.7-14.0) 14.0 (6.0-16.0)
Nominal heating capacity (min-max) kW 14.0 (5.0-18.0) 16.0 (5.0-20.0)
EER (*) 3.81 3.41
COP (*) 4.55 4.23
Minimum - Maximum indoor units
connectable
- 1 - 6 1 - 6
Minimum - Maximum connected ca-
pacity
% 50% -120% 50% -120%
Noise level cooling (sound pressure) 
(night mode)
dB(A) 48 (44) 48 (45)
Noise level heating (sound pressure) dB(A) 50 50
Noise level (sound power) dB(A) 66 67
Air ow m
3
/min 90 100
Dimensions (H x W x D) mm 1380 x 950 x 370 1380 x 950 x 370
Net weight kg 103 103
Recommended circuit breaker A 32 32
Starting current A Less than maximum current Less than maximum current
Maximum current A 28.0 28.0
Running current cooling A 13.8 17.5
Running current heating A 12.9 16.0
Power cable size  (according to EN 
60335-1)
quantity x
mm
2
3 x 6.0 3 x 6.0
Transmitting cable size between in-
door unit and outdoor unit
quantity x
mm
2
2 x 0.75 2 x 0.75
Piping diameter (liquid / gas) mm (inch) Ø9.53 (3/8) / Ø15.88 (5/8) Ø9.53 (3/8) / Ø15.88 (5/8)
Minimum piping length m 5 5
Maximum piping length chargeless m 30 30
Maximum piping length (additional 
refrigerant charge needed)
m (g/m) 75 (60) 75 (60)
Height difference (O.U. higher / O.U. 
lower)
m 30 / 20 30 / 20
Working range (cooling // heating) °C
-5 / +46 (DB) //
 -20 / +15(WB)
-5 / +46 (DB) //
 -20 / +15(WB)
Refrigerant - R410A R410A
Refrigerant charge before shipment kg 4.2 4.2
Compressor type - Scroll DC Inverter driven Scroll DC Inverter driven
Remote control model (Optional) PC-ART / PC-ARF PC-ART / PC-ARF
 (*) 
COP and EER data are specied for RCI-FSN3 indoor units combination
TCGB0079_rev0_11-2012.indb 34 29/01/2013 14:26:59