Technical Information
General data
IVX Premium series
TCGB0079 rev.0 - 01/2013
33
3.2 IVX Premium series
3.2.1 General specications
1~ 230V 50Hz
OUTDOOR UNITS RAS-2HVNP RAS-2.5HVNP RAS-3HVNPE RAS-4HVNPE
Power supply - 1~ 230V 50Hz 1~ 230V 50Hz 1~ 230V 50Hz 1~ 230V 50Hz
Nominal cooling capacity (min-max) kW 5.0 (2.2-5.6) 5.6 (2.2-6.3) 7.1 (3.2-8.0) 10.0 (4.5-11.2)
Nominal heating capacity (min-max) kW 5.6 (2.2-7.1) 6.3 (2.2-8.0) 8.0 (3.5-10.6) 11.2 (5.0-14.0)
EER (*) 4.03 3.97 4.49 4.68
COP (*) 4.68 4.92 4.88 5.16
Minimum - Maximum indoor units
connectable
- 1 - 2 1 - 2 1 - 3 1 - 5
Minimum - Maximum connected ca-
pacity
% 90% - 110% 90% - 110% 50% -120% 50% -120%
Noise level cooling (sound pressure)
(night mode)
dB(A) 44 (42) 45 (43) 46 (42) 47 (43)
Noise level heating (sound pressure) dB(A) 46 47 48 49
Noise level (sound power) dB(A) 62 63 64 65
Air ow m
3
/min 40.6 40.6 45 80
Dimensions (H x W x D) mm 600 x 792 x 300 600 x 792 x 300 800 x 950 x 370 1380 x 950 x 370
Net weight kg 41 41 66 103
Recommended circuit breaker A 16 20 20 32
Starting current A
Less than maxi-
mum current
Less than maxi-
mum current
Less than maxi-
mum current
Less than maxi-
mum current
Maximum current A 12.0 14.0 19.0 28.0
Running current cooling A 5.3 5.9 6.7 8.8
Running current heating A 5.1 5.9 6.9 9.0
Power cable size (according to EN
60335-1)
quantity x
mm
2
3 x 2.5 3 x 4.0 3 x 4.0 3 x 6.0
Transmitting cable size between in-
door unit and outdoor unit
quantity x
mm
2
2 x 0.75 2 x 0.75 2 x 0.75 2 x 0.75
Piping diameter (liquid / gas) mm (inch)
Ø6.35 (1/4) /
Ø12.7 (1/2)
Ø6.35 (1/4) /
Ø12.7 (1/2)
Ø9.53 (3/8) /
Ø15.88 (5/8)
Ø9.53 (3/8) /
Ø15.88 (5/8)
Minimum piping length m 5 5 5 5
Maximum piping length chargeless m
30
(0 m for 2 indoor
units system)
30
(0 m for 2 indoor
units system)
30 30
Maximum piping length (additional
refrigerant charge needed)
m (g/m) 50 (30) 50 (30
(1)
) 50 (40) 75 (60)
Height difference (O.U. higher / O.U.
lower)
m 30 / 20 30 / 20 30 / 20 30 / 20
Working range (cooling // heating) °C
-5 / +46 (DB) //
-20 / +15(WB)
-5 / +46 (DB) //
-20 / +15(WB)
-5 / +46 (DB) //
-20 / +15(WB)
-5 / +46 (DB) //
-20 / +15(WB)
Refrigerant - R410A R410A R410A R410A
Refrigerant charge before shipment kg 1.6 1.6 2.3 4.1
Compressor type -
Scroll DC Inverter
driven
Scroll DC Inverter
driven
Rotary DC Inverter
driven
Scroll DC Inverter
driven
Remote control model (Optional) PC-ART / PC-ARF PC-ART / PC-ARF PC-ART / PC-ARF PC-ART / PC-ARF
(*)
COP and EER data are specied for RCI-FSN3 indoor units combination
(1) For 2 indoor units system the additional refrigerant charge needed is 24 g/m
3