Technical Information

General data
General information
TCGB0079 rev.0 - 01/2013
32
3.1 General information
3.1.1 Combination with indoor units
All of the outdoor units described in this manual are combined with indoor units as indicated in the following table:
Outdoor units Indoor units Complementary system
IVX Premium / IVX Standard
RCI
KPI
KPI Active
DX-Interface
RCIM
RCD
RPC
RPI
RPIM
RPK
RPF
RPFI
3.1.2 Considerations
1 The nominal cooling and heating capacity is the combined capacity of the outdoor and indoor units system and is based
on the EN14511, with the following operating conditions.
Operating conditions Cooling Heating
Indoor air inlet temperature
DB 32.0 °C 20.0 °C
WB 19.0 °C
Outdoor air inlet temperature
DB 35.0 °C 7.0 °C
WB 6.0 °C
DB: Dry Bulb; WB: Wet Bulb
Piping length: 7.5 meters; Piping lift: 0 meters
2 The tables show a 1 indoor unit system, 2 units system for 8, 10 and 4 units system for 12HP.
3 The SEER, SCOP, EER and COP are specied in the outdoor unit in combination with the referred indoor unit.
4 The sound pressure level were measured in an anechoic chamber, so reected sound should be taken into considera-
tion when installing the unit. Test were carried out under the following conditions.
•  Measurement point located: 1.5 m from oor level and 1 m from the unit front surface.
•  Units working with their nominal supply voltage.
5 Sound power levels were measured in a reverberant room, in accordance with the standard EN12102. Used environ-
ment conditions are the same that specied in EN14511 for performance test.
6 SEER and SCOP are according to EN 14825