Technical Information

Electrical wiring
TCGB0079 rev.0 - 01/2013
140
10.4 H-LINK II system
The H-LINK II is the wiring connection system between units.
The H-LINK II wiring system only needs:
•  Two transmission wires connecting each indoor and outdoor unit for a total of 64 refrigerant cycles.
•  Connection wiring for all indoor and outdoor units in series.
C A U T I O N
•  TheH-LINKIIsystemcannotbeappliedtothemodelswiththeoldcycle,nortounitswithanoldtransmission.
10.4.1 Features
•  The total wiring length is considerably reduced compared to traditional connections.
•  Only one connection is required for the wiring between the indoor and outdoor units.
•  The wiring connection of the complementary central control devices is easy.
N O T E
•  CSNETWEBiscentralizedcontrolsystemwhichallowstheinstallationtobecontrolledremotely.Itcanbe
connectedatanypointofthelocalcorporatenetwork,orevenviatheInternet.
10.4.2 Specications
A: outdoor unit.
B: indoor unit.
C: a refrigerant cycle.
D: transmission cables.
E: refrigerant piping.
•  Transmission cable: 2-wire.
•  Polarity of transmission cable: non-polar wire.
•  Maximum number of indoor units that can be connected: 4
units per cycle and 160 units per H-LINK II system.
•  Maximum wiring length: total 1000 m (including CSNET WEB).
•  It is possible to increase the maximum wiring length up to
5000 m by using up to four PSC-5HR units.
A
B
C
D
E
•  Recommended cable: shielded twisted pair cable, over 0.75 mm
2
 (Equivalent to KPEV-S).
•  Voltage: 5 V DC.
C A U T I O N
•  FortheH-LINKIIsystemmustusetwistedshieldedpaircableorshieldedpaircable.
TCGB0079_rev0_11-2012.indb 140 29/01/2013 14:27:41