Technical Information

Electrical wiring
TCGB0079 rev.0 - 01/2013
138
10.3 Common wiring
10.3.1 Electrical wiring between outdoor and indoor unit
•  Connect the electrical wires between the indoor unit and the outdoor unit as show in the gure.
•  When installing the electrical wiring, follow local codes and regulations.
•  The refrigerant piping and the control wiring are connected to the units in the same refrigerant cycle.
•  Use twist pair wire (more than 0.75 mm
2
) for operation wiring between the outdoor unit and indoor unit, and operation 
wiring between indoor unit and indoor unit.
•  Use a 2-core wire for the operating line (do not use wire with more than 3 cores).
•  Use shielded wires for intermediate wiring to protect the units from noise interference at lengths of less than 300 m.
The size must comply with local code.
•  Open a hole near the connection hole of power source wiring when multiple outdoor units are connected from a single
power source line.
•  The recommended breaker sizes are detailed in the Wire size section.
•  In the case that a conduit tube for eld-wiring is not used, x rubber bushes with adhesive on the panel.
•  All eld wiring and equipment must comply with local and international codes.
•  H-LINK twist pair shielded cable must be grounded in the outdoor unit side.
N O T E
•  Takecarewiththeconnectionoftheoperatingline.IncorrectconnectionmaycauseafailureofthePCB.
Power source from the outdoor unit to the indoor unit Independent power source of outdoor unit and indoor unit
3
3
3
L1 L2 L3 NL1 L2 L3 N
L1 L2 L3 N
No. 0 System
Outdoor unit
No. 0 System
Outdoor unit
Operating Line
(Shielded Pair Cable)
DC5V (Non-Pole Transmission,
H-LINK System)
Remote Control Switch
(Twisted  Shielded  Pair 
Cable)
Operating Line
(Twisted Shielded 
Pair Cable)
DC5V (Non-Pole 
Transmission, H-LINK 
System)
Indoor Unit
Indoor Unit
Terminal board
Circuit Breaker
Earthleakage Breaker
Field Wiring
Field supplied
Optional Accessory
Remote Control Switch
(Twisted  Shielded  Pair 
Cable)
Indoor Unit
Indoor Unit
TB: Terminal board
CB: Circuit breaker (eld supplied)
ELB: Earthleakage breaker (eld supplied)
A: Power source from the outdoor unit to the indoor unit
TCGB0079_rev0_11-2012.indb 138 29/01/2013 14:27:40