Technical Information
General dimensions
TCGB0079 rev.0 - 01/2013
99
200
300
0 < L ≤ 1/2 H A ≥ 500
1/2 H < L ≤ H A ≥ 1000
≤ 300
f) In case that surrounding wall exist (serial units)
0 < L ≤ 1/2 A ≥ 500
1/2 H < L ≤ H A ≥ 1000
A
L
1000
0 < L ≤ 1/2 H A ≥ 200
1/2 H < L ≤ H A ≥ 350
g) Horizontal (multiple units) h) Vertical (multiple units)
0 < L ≤ 1/2 H A ≥ 100
1/2 H < L ≤ H A ≥ 200
≥ 1000
≥ 400
≥ 2000
≥ 250
400
≥ 250
≥ 250
400
250
≥ 250
- Do not stack more than two units in height.
- Close gap (*) to avoid recirculating discharge air ow.
7.2.3 RAS-(3-12)H(V)N(P/C)(E)
(Unit: mm)
Blocked in Inlet Side
Upper Side Open
Single Installation Multiple Installation (Two units or more)
200 or more of the back space is acceptable when the right and left
sides are open.
Dimensions in ( ) shows numbers especially for RAS-3H(V)N(P/C)E.
Allow 100 mm of space between units. Leave open both right and left
sides.
Dimensions in ( ) shows numbers especially for RAS-3H(V)N(P/C)E.