12. Maintenance notes
456
SMGB0079 rev.0 - 01/2013
12.1 General notes
12.1.1 Checking the power source and the wiring connection
Check the following items in the case of abnormal operation:
No. Check item Procedure
1
Is the breaker of the fuse cut
out?
Check the secondary voltage of the breaker and the fuse by means of a tester.
2
Is the secondary power source
on the transformer correct?
Disconnect the secondary side of the transformer and check the voltage by means of a tester.
Indoor unit
transformer
Secondary
side
Primary side
220, 230 or
240 V
Circuit and voltage
12 V
12 V
3
Is the wiring loosened or inco-
rrectly connected?
Check the wiring connection on the PCB.
Thermistor connectors
Connector of the remote control cable
Connector of the transformer
Each connector in a high-voltage circuitCheck the connectors according to the electrical wiring
diagram.
12.1.2 Burnt-out compressor due to an insufcient refrigerant charge
Question and answer for the eld work
Example 1: Burnt-out compressor due to an insufcient refrigerant charge
Phenomenon
After commissioning the alarm code “08” sometimes occurred and the compressors were burnt out after operating for two
months.
Cause
The refrigerant piping work was performed during the summer season. The additional refrigerant was not sufciently
charged from the discharge gas side.
This insufcient refrigerant charge resulted in the overheating of the discharge gas and the oil deterioration which was
nally due to the separated operation despite the alarm code “08”.
Countermeasure
1 The compressor was replaced with a new compressor.
2 The correct refrigerant amount was charged according to the refrigerant piping length and the connected indoor units.
Remarks
Additional refrigerant charge: Open the liquid stop valves slightly when you charge the additional refrigerant from the
check joint of the liquid stop valves (the discharge gas side) during the cooling process. If the liquid stop valve is fully open
it is difcult to charge the additional refrigerant. Do not charge the refrigerant from the gas stop valve.