Service Manual

Table Of Contents
10. Servicing
401
SMGB0079 rev.0 - 01/2013
10
10.4.1.8 Removing the High pressure switch and Pressure switch for control
RAS-4H(V)NCE
1  Remove the service cover and the bottom service cover following Removing service cover, and Removing bottom
service cover and rear cover.
2  Collect the refrigerant from the check joint according to Removing the compressor, in this chapter.
3  Remove the soundproof cover on the compressor.
4  Disconnect the Faston Terminals of High Pressure Switch and Pressure sensor for PD control.
5  Remove the high pressure switch and the pressure switch for control from the brazed part of discharge piping.
Discharge pipe
Electrical Box
Upper cover
High pressure
switch
Pressure sensor
for PD control
Brazing
part
RAS-(5-6)H(V)NCE
1  Remove the service cover, the bottom service cover and rear cover following Removing service cover and Removing
bottom service cover and rear cover.
2  Collect the refrigerant from the check joint according to Removing the compressor, in this chapter.
3  Remove the soundproof cover on the compressor.
4  Disconnect the Faston Terminals of High
Pressure Switch and Pressure sensor for PD
control.
5  Remove the high pressure switch and the
pressure switch for control from the brazed
part of discharge piping.
N O T E
Bewarethecoverscrewsdonotdamagethe
wirings when performing the procedure in
reverseway.
Electrical Box
Upper cover