Service Manual
Table Of Contents
- Contents
- 1. General information
- 2. Unit Installation
- 3. Piping work and refrigerant charge
- 4. Electrical wiring
- 4.1 General notes
- 4.2 Electrical wiring connection for the outdoor unit
- 4.3 Setting the DIP switches for the outdoor unit
- 4.4 Common wiring
- 4.5 H-LINK II system
- 4.6 System Control
- 4.7 Electrical wiring diagrams
- 4.7.1 RAS-(2-2.5)HVNP / RAS-3HVNC (1~ 230V 50Hz)
- 4.7.2 RAS-3HVNPE (1~ 230V 50Hz)
- 4.7.3 RAS-(4-6)HVNPE (1~ 230V 50Hz)
- 4.7.4 RAS-(4-6)HNPE (3N~ 400V 50Hz)
- 4.7.5 RAS-(4-6)HVNCE (1N~ 230V 50Hz)
- 4.7.6 RAS-(4-6)HNCE (3N~ 400V 50Hz)
- 4.7.7 RAS-(8-10)HN(P/C)E (3N~ 400V 50Hz)
- 4.7.8 RAS-12HNP (3N~ 400V 50Hz) - Preliminary data
- 4.7.9 RAS-12HNC (3N~ 400V 50Hz) - Preliminary data
- 5. Control System
- 5.1 Device control system
- 5.2 Outdoor units PCB
- 5.3 Protection and safety control
- 5.4 Standard operation sequence
- 5.5 Standard control functions
- 5.5.1 Freezing protection during cooling process or dry operation
- 5.5.2 Prevention Control for High Pressure Increase during Cooling Operation
- 5.5.3 Prevention control for excessively high discharge gas temperature
- 5.5.4 Activation for protection device control
- 5.5.5 Preheating control of compressor
- 5.5.6 Prevention control for high pressure increase
- 6. Optional functions
- 7. Test run
- 7.1 Checking procedure before the test run
- 7.2 Test run procedure using the remote control switch (PC-ART)
- 7.3 Test run procedure using the remote control switch (PC-ARF)
- 7.4 Test run procedure using the wireless remote control switch (PC-LH3A/B)
- 7.5 Test run procedure from the outdoor unit side
- 7.6 Check list
- 8. Troubleshooting
- 8.1 Initial troubleshooting
- 8.2 Troubleshooting procedure
- 8.3 Troubleshooting in check mode
- 8.4 Checking procedure for main parts
- 8.4.1 Procedure for checking the DIP-IPM inverter for indoor and outdoor units
- 8.4.2 Checking capacitors CB1 & CB2.
- 8.4.3 Fault diagnosis of DC fan motor.
- 8.4.4 Checking procedure for the electronic expansion valve for indoor and outdoor units
- 8.4.5 Checking procedure for AC fan motor
- 8.4.6 Checking procedure for other parts
- 9. Spare parts
- 10. Servicing
- 10.1 Introduction
- 10.2 Servicing for Outdoor Units RAS-(2-2.5)HVNP and RAS-3HVNC
- 10.3 Servicing for Premium series
- 10.3.1 Outdoor unit RAS-3HVNPE
- 10.3.1.1 Removing service cover
- 10.3.1.2 Remove outlet grille
- 10.3.1.3 Removing upper cover
- 10.3.1.4 Removing bottom service cover and rear cover
- 10.3.1.5 Removing outdoor fan motor
- 10.3.1.6 Removing electrical box
- 10.3.1.7 Removing the compressor
- 10.3.1.8 Removing the High pressure switch and Pressure switch for control
- 10.3.1.9 Opening electrical box (P plate)
- 10.3.1.10 Removing Reversing valve coil
- 10.3.1.11 Removing electronic expansion valve coil
- 10.3.1.12 Removing solenoid valve coil (SVC)
- 10.3.1.13 Removing reversing valve
- 10.3.1.14 Removing Electronic expansion Valve and Solenoid Valve
- 10.3.1.15 Removing electrical components
- 10.3.1.16 Removing other electrical components
- 10.3.2 Outdoor units RAS-(4-6)H(V)NPE
- 10.3.2.1 Removing service cover
- 10.3.2.2 Removing air outlet grille
- 10.3.2.3 Removing upper cover
- 10.3.2.4 Removing the bottom service cover and rear cover
- 10.3.2.5 Removing outdoor fan motor
- 10.3.2.6 Removing electrical box
- 10.3.2.7 Removing the compressor
- 10.3.2.8 Removing the High pressure switch and Pressure switch for control
- 10.3.2.9 Opening electrical box (P plate)
- 10.3.2.10 Removing Reversing valve coil
- 10.3.2.11 Removing electronic expansion valve coil
- 10.3.2.12 Removing solenoid valve coil (SVA and SVC)
- 10.3.2.13 Removing reversing valve
- 10.3.2.14 Removing Electronic expansion Valve and Solenoid Valve
- 10.3.2.15 Removing electrical components
- 10.3.2.16 Removing other electrical components
- 10.3.3 Oudoor units RAS-(8-10)HNPE
- 10.3.3.1 Removing service cover
- 10.3.3.2 Removing air outlet grille
- 10.3.3.3 Removing upper cover
- 10.3.3.4 Removing the bottom service cover and rear cover
- 10.3.3.5 Removing outdoor fan motor
- 10.3.3.6 Removing electrical box
- 10.3.3.7 Removing the compressor
- 10.3.3.8 Removing High pressure switch and pressure switch for control
- 10.3.3.9 Opening electrical box (P-Mounting Plate)
- 10.3.3.10 Removing reversing valve coil
- 10.3.3.11 Removing electronic expansion valve coil
- 10.3.3.12 Removing solenoid valve coil (SVA and SVC)
- 10.3.3.13 Removing reversing valve
- 10.3.3.14 Removing Electronic expansion Valve and Solenoid Valve
- 10.3.3.15 Removing electrical components
- 10.3.3.16 Removing other electrical components
- 10.3.4 Outdoor Units RAS-12HNP
- 10.3.4.1 Removing service cover
- 10.3.4.2 Removing air outlet grille
- 10.3.4.3 Removing upper cover
- 10.3.4.4 Removing the bottom service cover and rear cover
- 10.3.4.5 Removing outdoor fan motor
- 10.3.4.6 Removing electrical box
- 10.3.4.7 Removing the compressor
- 10.3.4.8 Removing High pressure switch and pressure switch for control
- 10.3.4.9 Removing reversing and solenoid valves coils
- 10.3.4.10 Removing electronic expansion valve coil
- 10.3.4.11 Removing reversing valve
- 10.3.4.12 Removing Electronic expansion Valve and Solenoid Valve
- 10.3.4.13 Removing electrical components
- 10.3.4.14 Removing other electrical components
- 10.3.1 Outdoor unit RAS-3HVNPE
- 10.4 Servicing for Standard Series
- 10.4.1 Outdoor Units RAS-(4-6)H(V)NCE
- 10.4.1.1 Removing service cover
- 10.4.1.2 Remove outlet grille
- 10.4.1.3 Removing upper cover
- 10.4.1.4 Removing bottom service cover and rear cover
- 10.4.1.5 Removing outdoor fan motor
- 10.4.1.6 Removing electrical box
- 10.4.1.7 Removing the compressor
- 10.4.1.8 Removing the High pressure switch and Pressure switch for control
- 10.4.1.9 Opening electrical box (P plate)
- 10.4.1.10 Removing Reversing valve coil
- 10.4.1.11 Removing electronic expansion valve coil
- 10.4.1.12 Removing solenoid valve coil (SVA)
- 10.4.1.13 Removing reversing valve
- 10.4.1.14 Removing Electronic expansion valve and Solenoid valve
- 10.4.1.15 Removing electrical components
- 10.4.1.16 Removing other electrical components
- 10.4.2 Outdoor Units RAS-(8-10)HNCE
- 10.4.2.1 Removing service cover
- 10.4.2.2 Removing air outlet grille
- 10.4.2.3 Removing upper cover
- 10.4.2.4 Removing the bottom service cover and rear cover
- 10.4.2.5 Removing outdoor fan motor
- 10.4.2.6 Removing electrical box
- 10.4.2.7 Removing the compressor
- 10.4.2.8 Removing High pressure switch and pressure switch for control
- 10.4.2.9 Opening electrical box (P-Mounting Plate)
- 10.4.2.10 Removing reversing valve coil
- 10.4.2.11 Removing electronic expansion valve coil
- 10.4.2.12 Removing solenoid valve coil (SVA)
- 10.4.2.13 Removing reversing valve
- 10.4.2.14 Removing Electronic expansion Valve and Solenoid Valve
- 10.4.2.15 Removing electrical components
- 10.4.2.16 Removing other electrical components
- 10.4.3 Outdoor Units RAS-12HNC
- 10.4.3.1 Removing service cover
- 10.4.3.2 Removing air outlet grille
- 10.4.3.3 Removing upper cover
- 10.4.3.4 Removing the bottom service cover and rear cover
- 10.4.3.5 Removing outdoor fan motor
- 10.4.3.6 Removing electrical box
- 10.4.3.7 Removing High pressure switch and pressure switch for control
- 10.4.3.8 Opening electrical box (P-Mounting Plate)
- 10.4.3.9 Removing reversing and solenoid valves coils
- 10.4.3.10 Removing electronic expansion valve coil
- 10.4.3.11 Removing reversing valve
- 10.4.3.12 Removing Electronic expansion Valve and Solenoid Valve
- 10.4.3.13 Removing electrical components
- 10.4.3.14 Removing other electrical components
- 10.4.1 Outdoor Units RAS-(4-6)H(V)NCE
- 11. Electrial checks of main parts
- 12. Maintenance notes
- 12.1 General notes
- 12.1.1 Checking the power source and the wiring connection
- 12.1.2 Burnt-out compressor due to an insufficient refrigerant charge
- 12.1.3 Insufficient cooling performance when a long piping is applied
- 12.1.4 Abnormally high operation sound (in the ceiling type indoor unit).
- 12.1.5 Alarm code “31”
- 12.1.6 Not cooling well due to insufficient installation space for the outdoor unit
- 12.2 Maintenance work
- 12.3 Service and maintenance record
- 12.4 Service and maintenance record using the 7-segment display
- 12.5 Service and maintenance record by remote control switch
- 12.6 Pump-down method for replacing the compressor
- 12.1 General notes
- General information
- Safety
- Product guide
- Safety summary
- Transportation of outdoor unit
- Center of gravity
- Factory-supplied accessories for RAS-12HN(P/C)
- Installation space (Initial ckeck)
- Place provision
- Optional parts and installation
- General notes before performing pipe work
- Piping connection for outdoor unit
- Refrigerant piping range
- Refrigerant charge
- Caution in case of refrigerant leakage
- Piping work for compatibility with the piping of current installations where is used R22 or R407C.
- Drain piping
- General notes
- Electrical wiring connection for the outdoor unit
- Setting the DIP switches for the outdoor unit
- Common wiring
- H-LINK II system
- System Control
- Electrical wiring diagrams
- RAS-(2-2.5)HVNP / RAS-3HVNC (1~ 230V 50Hz)
- RAS-3HVNPE (1~ 230V 50Hz)
- RAS-(4-6)HVNPE (1~ 230V 50Hz)
- RAS-(4-6)HNPE (3N~ 400V 50Hz)
- RAS-(4-6)HVNCE (1N~ 230V 50Hz)
- RAS-(4-6)HNCE (3N~ 400V 50Hz)
- RAS-(8-10)HN(P/C)E (3N~ 400V 50Hz)
- RAS-12HNP (3N~ 400V 50Hz) - Preliminary data
- RAS-12HNC (3N~ 400V 50Hz) - Preliminary data
- Device control system
- Outdoor units PCB
- Protection and safety control
- Standard operation sequence
- Standard control functions
- Freezing protection during cooling process or dry operation
- Prevention Control for High Pressure Increase during Cooling Operation
- Prevention control for excessively high discharge gas temperature
- Activation for protection device control
- Preheating control of compressor
- Prevention control for high pressure increase
- Optional input and output signals (By 7-segment display)
- Optional functions (By 7-segment display)
- Optional functions (By remote control switch)
- Checking procedure before the test run
- Test run procedure using the remote control switch (PC-ART)
- Test run procedure using the remote control switch (PC-ARF)
- Test run procedure using the wireless remote control switch (PC-LH3A/B)
- Test run procedure from the outdoor unit side
- Check list
- Initial troubleshooting
- Troubleshooting procedure
- Troubleshooting in check mode
- Checking procedure for main parts
- RAS-(2-2.5)HVNP
- RAS-3HVNC
- RAS-3HVNPE
- RAS-(4-6)H(V)NPE
- RAS-(4-6)H(V)NCE
- RAS-(8-10)HN(P/C)E
- RAS-12HN(P/C)
- Introduction
- Servicing for Outdoor Units RAS-(2-2.5)HVNP and RAS-3HVNC
- Servicing for Premium series
- Outdoor unit RAS-3HVNPE
- Removing service cover
- Remove outlet grille
- Removing upper cover
- Removing bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing the compressor
- Removing the High pressure switch and Pressure switch for control
- Opening electrical box (P plate)
- Removing Reversing valve coil
- Removing electronic expansion valve coil
- Removing solenoid valve coil (SVC)
- Removing reversing valve
- Removing Electronic expansion Valve and Solenoid Valve
- Removing electrical components
- Removing other electrical components
- Outdoor units RAS-(4-6)H(V)NPE
- Removing service cover
- Removing air outlet grille
- Removing upper cover
- Removing the bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing the compressor
- Removing the High pressure switch and Pressure switch for control
- Opening electrical box (P plate)
- Removing Reversing valve coil
- Removing electronic expansion valve coil
- Removing solenoid valve coil (SVA and SVC)
- Removing reversing valve
- Removing Electronic expansion Valve and Solenoid Valve
- Removing electrical components
- Removing other electrical components
- Oudoor units RAS-(8-10)HNPE
- Removing service cover
- Removing air outlet grille
- Removing upper cover
- Removing the bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing the compressor
- Removing High pressure switch and pressure switch for control
- Opening electrical box (P-Mounting Plate)
- Removing reversing valve coil
- Removing electronic expansion valve coil
- Removing solenoid valve coil (SVA and SVC)
- Removing reversing valve
- Removing Electronic expansion Valve and Solenoid Valve
- Removing electrical components
- Removing other electrical components
- Outdoor Units RAS-12HNP
- Removing service cover
- Removing air outlet grille
- Removing upper cover
- Removing the bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing the compressor
- Removing High pressure switch and pressure switch for control
- Removing reversing and solenoid valves coils
- Removing electronic expansion valve coil
- Removing reversing valve
- Removing Electronic expansion Valve and Solenoid Valve
- Removing electrical components
- Removing other electrical components
- Outdoor unit RAS-3HVNPE
- Servicing for Standard Series
- Outdoor Units RAS-(4-6)H(V)NCE
- Removing service cover
- Remove outlet grille
- Removing upper cover
- Removing bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing the compressor
- Removing the High pressure switch and Pressure switch for control
- Opening electrical box (P plate)
- Removing Reversing valve coil
- Removing electronic expansion valve coil
- Removing solenoid valve coil (SVA)
- Removing reversing valve
- Removing Electronic expansion valve and Solenoid valve
- Removing electrical components
- Removing other electrical components
- Outdoor Units RAS-(8-10)HNCE
- Removing service cover
- Removing air outlet grille
- Removing upper cover
- Removing the bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing the compressor
- Removing High pressure switch and pressure switch for control
- Opening electrical box (P-Mounting Plate)
- Removing reversing valve coil
- Removing electronic expansion valve coil
- Removing solenoid valve coil (SVA)
- Removing reversing valve
- Removing Electronic expansion Valve and Solenoid Valve
- Removing electrical components
- Removing other electrical components
- Outdoor Units RAS-12HNC
- Removing service cover
- Removing air outlet grille
- Removing upper cover
- Removing the bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing High pressure switch and pressure switch for control
- Opening electrical box (P-Mounting Plate)
- Removing reversing and solenoid valves coils
- Removing electronic expansion valve coil
- Removing reversing valve
- Removing Electronic expansion Valve and Solenoid Valve
- Removing electrical components
- Removing other electrical components
- Outdoor Units RAS-(4-6)H(V)NCE
- Inverter
- Thermistor
- Electronic expansion valve
- High pressure protection device
- Noise filter (NF)
- Capacitor (CB1 CB2)
- Reactor (DCL)
- Scroll compressor
- General notes
- Checking the power source and the wiring connection
- Burnt-out compressor due to an insufficient refrigerant charge
- Insufficient cooling performance when a long piping is applied
- Abnormally high operation sound (in the ceiling type indoor unit).
- Alarm code “31”
- Not cooling well due to insufficient installation space for the outdoor unit
- Maintenance work
- Service and maintenance record
- Service and maintenance record using the 7-segment display
- Service and maintenance record by remote control switch
- Pump-down method for replacing the compressor

8. Troubleshooting
258
SMGB0079 rev.0 - 01/2013
Contents of the check mode 2
When more than three indoor units are connected to one remote control switch, the latest data of only the rst three indoor
units that are connected serially are displayed.
If you press the part “” of the TEMP switch, the next display appears. If you press the part “” of the TEMP switch, the
previous display appears.
Temperature indication
Indication of the category code
Indication of the temperature, etc
1
Indoor unit air inlet temperature at
thermistor (°C)
91
23
Corresponds to check mode 1 “b2”
2
Indoor unit discharge air tempera-
ture at thermistor (°C)
92
50
Corresponds to check mode 1 “b3”
3
Indoor unit heat exchanger liquid
pipe temperature
(freeze protection) (°C)
93
25
Corresponds to check mode 1 “b4”
4 Outdoor temperature (°C)
94
12
Corresponds to check mode 1 “b6”
5
Indoor unit heat exchanger gas
pipe temperature (°C)
95
25
Corresponds to check mode 1 “b7”
6
Evaporating temperature at
heating (°C)
96
03
Corresponds to check mode 1 “b8”
7 Control information
97
--
Corresponds to check mode 1 “b9”
8
Discharge gas temperature at the
top of compressor chamber (°C)
98
45
Corresponds to check mode 1 “bA”
Compressor pressure/frequency indication
9
Discharge pressure (high)
(x 0.1 MPa)
9g
18
Corresponds to check mode 1 “H1”
10
Suction pressure (low)
(x 0.01 MPa)
9A
04
Corresponds to check mode 1 “H2”
11 Control information
96
44
Corresponds to check mode 1 “H3”
12 Operating frequency (Hz)
9C
44
Corresponds to check mode 1 “H4”
Expansion opening indication
13
Indoor unit expansion valve
opening (%)
9d
20
Corresponds to check mode 1 “L1”
14
Outdoor unit expansion valve mv1
opening (%)
9E
gg
Corresponds to check mode 1 “L2”
Estimated electric current indication
15 Compressor running current (A)
9F
20
Corresponds to check mode 1 “P1”
Returns to temperature indication