8. Troubleshooting
258
SMGB0079 rev.0 - 01/2013
Contents of the check mode 2
When more than three indoor units are connected to one remote control switch, the latest data of only the rst three indoor
units that are connected serially are displayed.
If you press the part ” of the TEMP switch, the next display appears. If you press the part ” of the TEMP switch, the
previous display appears.
Temperature indication
Indication of the category code
Indication of the temperature, etc
1
Indoor unit air inlet temperature at
thermistor (°C)
91
23
Corresponds to check mode 1 “b2
2
Indoor unit discharge air tempera-
ture at thermistor (°C)
92
50
Corresponds to check mode 1 “b3
3
Indoor unit heat exchanger liquid
pipe temperature
(freeze protection) (°C)
93
25
Corresponds to check mode 1 “b4
4 Outdoor temperature (°C)
94
12
Corresponds to check mode 1 “b6
5
Indoor unit heat exchanger gas
pipe temperature (°C)
95
25
Corresponds to check mode 1 “b7
6
Evaporating temperature at
heating (°C)
96
03
Corresponds to check mode 1 “b8
7 Control information
97
--
Corresponds to check mode 1 “b9
8
Discharge gas temperature at the
top of compressor chamber (°C)
98
45
Corresponds to check mode 1 “bA
Compressor pressure/frequency indication
9
Discharge pressure (high)
(x 0.1 MPa)
9g
18
Corresponds to check mode 1 “H1
10
Suction pressure (low)
(x 0.01 MPa)
9A
04
Corresponds to check mode 1 “H2
11 Control information
96
44
Corresponds to check mode 1 “H3
12 Operating frequency (Hz)
9C
44
Corresponds to check mode 1 “H4
Expansion opening indication
13
Indoor unit expansion valve
opening (%)
9d
20
Corresponds to check mode 1 “L1
14
Outdoor unit expansion valve mv1
opening (%)
9E
gg
Corresponds to check mode 1 “L2
Estimated electric current indication
15 Compressor running current (A)
9F
20
Corresponds to check mode 1 “P1
Returns to temperature indication