Abnormal operation occurrence counter
15
Abnormal operation occurrence
counter
E1
01
Countable up to 99.
Over 99 times, “99” is always displayed.
N O T E
• If a transmission error continues for three mi-
nutes,oneisaddedtotheoccurrencecounter.
• The memorized data can be cancelled by the
methodwhichisexplainedinsectionSelf-check-
ing procedure of PCB using the remote control
switch.
16
Instantaneous power failure occu-
rrence counter in indoor unit
E2
00
17
Transmission error occurrence
counter between remote control
switch and indoor unit
E3
00
18
Abnormal operation occurrence
counter on inverter
E4
00
Indication of automatic louver condition
19 Louver sensor
F1
00
00: Normal
FF: Abnormal
Compressor pressure/frequency indication
20
Discharge pressure (high)
(x 0.1 MPa)
H1
18
21
Suction pressure (low)
(x 0.01 MPa)
H2
04
22 Control information
H3
44
This is an indication for internal information for the remote
control switch. This does not have any specic meaning
23 Operation frequency (Hz)
H4
44
This is an indication for frequency of inverter
Indoor unit capacity indication
The capacity of the indoor unit is indicated as shown in the
table below.
Capacity code of indoor unit
Indication code Equivalent capacity (HP)
06 0.8
08 1.0
10 1.3
13 1.5
14 1.8
16 2.0
18 2.3
20 2.5
22 2.8
26 3.0
32 4.0
40 5.0
48 6.0
64 8.0
80 10.0
24 Indoor unit capacity
J1
08
25 Outdoor unit code
J2
Fn
26
Refrigerant cycle number (Indoor
unit shipment DSW5+RSW2)
J3
01
27
Refrigerant cycle number (Indoor
unit shipment DSW5+RSW2)
J4
00
n” indicates the total number of Indoor Units:
1~g A b C d E F U
1~9 10 11 12 13 14 15 16
J3: 01 ~ 64 (Decimal code)
J4: 00 ~ 3F (Hexadecimal code)