8. Troubleshooting
244
SMGB0079 rev.0 - 01/2013
Alarm code
54
Abnormality of inverter n temperature (RAS-3HVNPE / RAS-(4-6)H(V)N(P/C)E)
The RUN LED ickers and “ALARM” is displayed on the remote control switch.
The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit
number and the alarm code are displayed on the display of the outdoor unit PCB.
- This alarm code is indicated after the operation is stpped when the following condition occurs three times within 30
minutes. The retry operation is performed twice.
Conditions:
When the temperature of the thermistor for inverter n excess 80 °C (RAS-3HVNPE)
When the temperature inside the transistor module excess 90 °C (RAS-(4-6)H(V)NPE).
When the temperature of the thermistor for inverter n excess 92 °C (RAS-(4-6)H(V)NCE)
Restart operation.
Does it trip soon?
Is the heat exchanger of
outdoor unit clogged?
No
Replace inverter PCB. *1)
Remove clogging.
Yes
Yes
No
Replace inverter PCB. *1)
N O T E
1*):Performthehighvoltagedischargeworkbyreferringtothe itemProcedureof checkingothermainparts,
beforecheckingandreplacingtheinvertercomponents.