8. Troubleshooting
226
SMGB0079 rev.0 - 01/2013
Alarm code
38
Abnormality of Protective Circuit for Protection (Outdoor Unit)
The RUN LED ickers and “ALARM” is displayed on the remote control switch.
The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit
number and the alarm code are displayed on the display of the outdoor unit PCB.
- The alarm code appears if approx. DC12V is supplied to the DIP-IPM connector (see table below) when the inverter
operation is commanded (after ve seconds following activation of the remote control switch).
Place the tester as shown in the diagram below to check the connector of PCN401. The connector shall remain inserted.
DC12V will constantly be detected and disturb the diagnosis if the connector of PCN401 is pulled out.
RAS-(2-2.5)HVNP / RAS-3HVNC
RAS-(3-6)H(V)N(P/C)E / RAS-(8-12)HN(P/C)(E)
The alarm code appears if AC 200V or AC 240V is supplied to the connector on the outdoor unit PCB (see table below)
while Y52C is OFF or CMC1 is open.
Connector No.
for Check
Connector PCN9
Pin No. #1 and #3
Phenomenon Cause Check item
Action
(Turn OFF Main Switch)
Faulty DIP-IPM Check DIP-IPM by seft-checking Replace DIP-IPM
N O T E
ThisalarmmayappeariftheFastonterminalofthehighpressureswitch(63H1)isimproperlyconnectedorda-
maged(open-circuitfault)whentheoperationisstarted.Besidesthis,checkalso“AlarmCode:02Activationof
OutdoorUnitProtectionDevice”.