Service Manual

Table Of Contents
8. Troubleshooting
222
SMGB0079 rev.0 - 01/2013
Alarm code
22
Abnormal operation of the thermistor for the outdoor temperature (outdoor unit ambient thermistor)
The RUN LED ickers and “ALARM” is displayed on the remote control switch.
The unit number, the alarm code and the unit code are alternately displayed on the set temperature section.
The unit number and the alarm code are displayed on the display of the outdoor unit PCB.
- This alarm code is displayed when the thermistor is short-circuited (less than 0.2 kΩ) or cut (greater than 500 kΩ)
during the operation.
P
C
Other than above
Phenomenon Cause Check item
Action
(Turn OFF Main Switch)
Faulty thermistor for the outdoor
unit ambient
Fault Check resistance Replace thermistor if faulty
Incorrect connection Check wiring to PCB Repair wiring and connections
Faulty PCB1
Replace PCB1 and check
operation
Replace PCB if faulty