Service Manual
Table Of Contents
- Contents
- 1. General information
- 2. Unit Installation
- 3. Piping work and refrigerant charge
- 4. Electrical wiring
- 4.1 General notes
- 4.2 Electrical wiring connection for the outdoor unit
- 4.3 Setting the DIP switches for the outdoor unit
- 4.4 Common wiring
- 4.5 H-LINK II system
- 4.6 System Control
- 4.7 Electrical wiring diagrams
- 4.7.1 RAS-(2-2.5)HVNP / RAS-3HVNC (1~ 230V 50Hz)
- 4.7.2 RAS-3HVNPE (1~ 230V 50Hz)
- 4.7.3 RAS-(4-6)HVNPE (1~ 230V 50Hz)
- 4.7.4 RAS-(4-6)HNPE (3N~ 400V 50Hz)
- 4.7.5 RAS-(4-6)HVNCE (1N~ 230V 50Hz)
- 4.7.6 RAS-(4-6)HNCE (3N~ 400V 50Hz)
- 4.7.7 RAS-(8-10)HN(P/C)E (3N~ 400V 50Hz)
- 4.7.8 RAS-12HNP (3N~ 400V 50Hz) - Preliminary data
- 4.7.9 RAS-12HNC (3N~ 400V 50Hz) - Preliminary data
- 5. Control System
- 5.1 Device control system
- 5.2 Outdoor units PCB
- 5.3 Protection and safety control
- 5.4 Standard operation sequence
- 5.5 Standard control functions
- 5.5.1 Freezing protection during cooling process or dry operation
- 5.5.2 Prevention Control for High Pressure Increase during Cooling Operation
- 5.5.3 Prevention control for excessively high discharge gas temperature
- 5.5.4 Activation for protection device control
- 5.5.5 Preheating control of compressor
- 5.5.6 Prevention control for high pressure increase
- 6. Optional functions
- 7. Test run
- 7.1 Checking procedure before the test run
- 7.2 Test run procedure using the remote control switch (PC-ART)
- 7.3 Test run procedure using the remote control switch (PC-ARF)
- 7.4 Test run procedure using the wireless remote control switch (PC-LH3A/B)
- 7.5 Test run procedure from the outdoor unit side
- 7.6 Check list
- 8. Troubleshooting
- 8.1 Initial troubleshooting
- 8.2 Troubleshooting procedure
- 8.3 Troubleshooting in check mode
- 8.4 Checking procedure for main parts
- 8.4.1 Procedure for checking the DIP-IPM inverter for indoor and outdoor units
- 8.4.2 Checking capacitors CB1 & CB2.
- 8.4.3 Fault diagnosis of DC fan motor.
- 8.4.4 Checking procedure for the electronic expansion valve for indoor and outdoor units
- 8.4.5 Checking procedure for AC fan motor
- 8.4.6 Checking procedure for other parts
- 9. Spare parts
- 10. Servicing
- 10.1 Introduction
- 10.2 Servicing for Outdoor Units RAS-(2-2.5)HVNP and RAS-3HVNC
- 10.3 Servicing for Premium series
- 10.3.1 Outdoor unit RAS-3HVNPE
- 10.3.1.1 Removing service cover
- 10.3.1.2 Remove outlet grille
- 10.3.1.3 Removing upper cover
- 10.3.1.4 Removing bottom service cover and rear cover
- 10.3.1.5 Removing outdoor fan motor
- 10.3.1.6 Removing electrical box
- 10.3.1.7 Removing the compressor
- 10.3.1.8 Removing the High pressure switch and Pressure switch for control
- 10.3.1.9 Opening electrical box (P plate)
- 10.3.1.10 Removing Reversing valve coil
- 10.3.1.11 Removing electronic expansion valve coil
- 10.3.1.12 Removing solenoid valve coil (SVC)
- 10.3.1.13 Removing reversing valve
- 10.3.1.14 Removing Electronic expansion Valve and Solenoid Valve
- 10.3.1.15 Removing electrical components
- 10.3.1.16 Removing other electrical components
- 10.3.2 Outdoor units RAS-(4-6)H(V)NPE
- 10.3.2.1 Removing service cover
- 10.3.2.2 Removing air outlet grille
- 10.3.2.3 Removing upper cover
- 10.3.2.4 Removing the bottom service cover and rear cover
- 10.3.2.5 Removing outdoor fan motor
- 10.3.2.6 Removing electrical box
- 10.3.2.7 Removing the compressor
- 10.3.2.8 Removing the High pressure switch and Pressure switch for control
- 10.3.2.9 Opening electrical box (P plate)
- 10.3.2.10 Removing Reversing valve coil
- 10.3.2.11 Removing electronic expansion valve coil
- 10.3.2.12 Removing solenoid valve coil (SVA and SVC)
- 10.3.2.13 Removing reversing valve
- 10.3.2.14 Removing Electronic expansion Valve and Solenoid Valve
- 10.3.2.15 Removing electrical components
- 10.3.2.16 Removing other electrical components
- 10.3.3 Oudoor units RAS-(8-10)HNPE
- 10.3.3.1 Removing service cover
- 10.3.3.2 Removing air outlet grille
- 10.3.3.3 Removing upper cover
- 10.3.3.4 Removing the bottom service cover and rear cover
- 10.3.3.5 Removing outdoor fan motor
- 10.3.3.6 Removing electrical box
- 10.3.3.7 Removing the compressor
- 10.3.3.8 Removing High pressure switch and pressure switch for control
- 10.3.3.9 Opening electrical box (P-Mounting Plate)
- 10.3.3.10 Removing reversing valve coil
- 10.3.3.11 Removing electronic expansion valve coil
- 10.3.3.12 Removing solenoid valve coil (SVA and SVC)
- 10.3.3.13 Removing reversing valve
- 10.3.3.14 Removing Electronic expansion Valve and Solenoid Valve
- 10.3.3.15 Removing electrical components
- 10.3.3.16 Removing other electrical components
- 10.3.4 Outdoor Units RAS-12HNP
- 10.3.4.1 Removing service cover
- 10.3.4.2 Removing air outlet grille
- 10.3.4.3 Removing upper cover
- 10.3.4.4 Removing the bottom service cover and rear cover
- 10.3.4.5 Removing outdoor fan motor
- 10.3.4.6 Removing electrical box
- 10.3.4.7 Removing the compressor
- 10.3.4.8 Removing High pressure switch and pressure switch for control
- 10.3.4.9 Removing reversing and solenoid valves coils
- 10.3.4.10 Removing electronic expansion valve coil
- 10.3.4.11 Removing reversing valve
- 10.3.4.12 Removing Electronic expansion Valve and Solenoid Valve
- 10.3.4.13 Removing electrical components
- 10.3.4.14 Removing other electrical components
- 10.3.1 Outdoor unit RAS-3HVNPE
- 10.4 Servicing for Standard Series
- 10.4.1 Outdoor Units RAS-(4-6)H(V)NCE
- 10.4.1.1 Removing service cover
- 10.4.1.2 Remove outlet grille
- 10.4.1.3 Removing upper cover
- 10.4.1.4 Removing bottom service cover and rear cover
- 10.4.1.5 Removing outdoor fan motor
- 10.4.1.6 Removing electrical box
- 10.4.1.7 Removing the compressor
- 10.4.1.8 Removing the High pressure switch and Pressure switch for control
- 10.4.1.9 Opening electrical box (P plate)
- 10.4.1.10 Removing Reversing valve coil
- 10.4.1.11 Removing electronic expansion valve coil
- 10.4.1.12 Removing solenoid valve coil (SVA)
- 10.4.1.13 Removing reversing valve
- 10.4.1.14 Removing Electronic expansion valve and Solenoid valve
- 10.4.1.15 Removing electrical components
- 10.4.1.16 Removing other electrical components
- 10.4.2 Outdoor Units RAS-(8-10)HNCE
- 10.4.2.1 Removing service cover
- 10.4.2.2 Removing air outlet grille
- 10.4.2.3 Removing upper cover
- 10.4.2.4 Removing the bottom service cover and rear cover
- 10.4.2.5 Removing outdoor fan motor
- 10.4.2.6 Removing electrical box
- 10.4.2.7 Removing the compressor
- 10.4.2.8 Removing High pressure switch and pressure switch for control
- 10.4.2.9 Opening electrical box (P-Mounting Plate)
- 10.4.2.10 Removing reversing valve coil
- 10.4.2.11 Removing electronic expansion valve coil
- 10.4.2.12 Removing solenoid valve coil (SVA)
- 10.4.2.13 Removing reversing valve
- 10.4.2.14 Removing Electronic expansion Valve and Solenoid Valve
- 10.4.2.15 Removing electrical components
- 10.4.2.16 Removing other electrical components
- 10.4.3 Outdoor Units RAS-12HNC
- 10.4.3.1 Removing service cover
- 10.4.3.2 Removing air outlet grille
- 10.4.3.3 Removing upper cover
- 10.4.3.4 Removing the bottom service cover and rear cover
- 10.4.3.5 Removing outdoor fan motor
- 10.4.3.6 Removing electrical box
- 10.4.3.7 Removing High pressure switch and pressure switch for control
- 10.4.3.8 Opening electrical box (P-Mounting Plate)
- 10.4.3.9 Removing reversing and solenoid valves coils
- 10.4.3.10 Removing electronic expansion valve coil
- 10.4.3.11 Removing reversing valve
- 10.4.3.12 Removing Electronic expansion Valve and Solenoid Valve
- 10.4.3.13 Removing electrical components
- 10.4.3.14 Removing other electrical components
- 10.4.1 Outdoor Units RAS-(4-6)H(V)NCE
- 11. Electrial checks of main parts
- 12. Maintenance notes
- 12.1 General notes
- 12.1.1 Checking the power source and the wiring connection
- 12.1.2 Burnt-out compressor due to an insufficient refrigerant charge
- 12.1.3 Insufficient cooling performance when a long piping is applied
- 12.1.4 Abnormally high operation sound (in the ceiling type indoor unit).
- 12.1.5 Alarm code “31”
- 12.1.6 Not cooling well due to insufficient installation space for the outdoor unit
- 12.2 Maintenance work
- 12.3 Service and maintenance record
- 12.4 Service and maintenance record using the 7-segment display
- 12.5 Service and maintenance record by remote control switch
- 12.6 Pump-down method for replacing the compressor
- 12.1 General notes
- General information
- Safety
- Product guide
- Safety summary
- Transportation of outdoor unit
- Center of gravity
- Factory-supplied accessories for RAS-12HN(P/C)
- Installation space (Initial ckeck)
- Place provision
- Optional parts and installation
- General notes before performing pipe work
- Piping connection for outdoor unit
- Refrigerant piping range
- Refrigerant charge
- Caution in case of refrigerant leakage
- Piping work for compatibility with the piping of current installations where is used R22 or R407C.
- Drain piping
- General notes
- Electrical wiring connection for the outdoor unit
- Setting the DIP switches for the outdoor unit
- Common wiring
- H-LINK II system
- System Control
- Electrical wiring diagrams
- RAS-(2-2.5)HVNP / RAS-3HVNC (1~ 230V 50Hz)
- RAS-3HVNPE (1~ 230V 50Hz)
- RAS-(4-6)HVNPE (1~ 230V 50Hz)
- RAS-(4-6)HNPE (3N~ 400V 50Hz)
- RAS-(4-6)HVNCE (1N~ 230V 50Hz)
- RAS-(4-6)HNCE (3N~ 400V 50Hz)
- RAS-(8-10)HN(P/C)E (3N~ 400V 50Hz)
- RAS-12HNP (3N~ 400V 50Hz) - Preliminary data
- RAS-12HNC (3N~ 400V 50Hz) - Preliminary data
- Device control system
- Outdoor units PCB
- Protection and safety control
- Standard operation sequence
- Standard control functions
- Freezing protection during cooling process or dry operation
- Prevention Control for High Pressure Increase during Cooling Operation
- Prevention control for excessively high discharge gas temperature
- Activation for protection device control
- Preheating control of compressor
- Prevention control for high pressure increase
- Optional input and output signals (By 7-segment display)
- Optional functions (By 7-segment display)
- Optional functions (By remote control switch)
- Checking procedure before the test run
- Test run procedure using the remote control switch (PC-ART)
- Test run procedure using the remote control switch (PC-ARF)
- Test run procedure using the wireless remote control switch (PC-LH3A/B)
- Test run procedure from the outdoor unit side
- Check list
- Initial troubleshooting
- Troubleshooting procedure
- Troubleshooting in check mode
- Checking procedure for main parts
- RAS-(2-2.5)HVNP
- RAS-3HVNC
- RAS-3HVNPE
- RAS-(4-6)H(V)NPE
- RAS-(4-6)H(V)NCE
- RAS-(8-10)HN(P/C)E
- RAS-12HN(P/C)
- Introduction
- Servicing for Outdoor Units RAS-(2-2.5)HVNP and RAS-3HVNC
- Servicing for Premium series
- Outdoor unit RAS-3HVNPE
- Removing service cover
- Remove outlet grille
- Removing upper cover
- Removing bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing the compressor
- Removing the High pressure switch and Pressure switch for control
- Opening electrical box (P plate)
- Removing Reversing valve coil
- Removing electronic expansion valve coil
- Removing solenoid valve coil (SVC)
- Removing reversing valve
- Removing Electronic expansion Valve and Solenoid Valve
- Removing electrical components
- Removing other electrical components
- Outdoor units RAS-(4-6)H(V)NPE
- Removing service cover
- Removing air outlet grille
- Removing upper cover
- Removing the bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing the compressor
- Removing the High pressure switch and Pressure switch for control
- Opening electrical box (P plate)
- Removing Reversing valve coil
- Removing electronic expansion valve coil
- Removing solenoid valve coil (SVA and SVC)
- Removing reversing valve
- Removing Electronic expansion Valve and Solenoid Valve
- Removing electrical components
- Removing other electrical components
- Oudoor units RAS-(8-10)HNPE
- Removing service cover
- Removing air outlet grille
- Removing upper cover
- Removing the bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing the compressor
- Removing High pressure switch and pressure switch for control
- Opening electrical box (P-Mounting Plate)
- Removing reversing valve coil
- Removing electronic expansion valve coil
- Removing solenoid valve coil (SVA and SVC)
- Removing reversing valve
- Removing Electronic expansion Valve and Solenoid Valve
- Removing electrical components
- Removing other electrical components
- Outdoor Units RAS-12HNP
- Removing service cover
- Removing air outlet grille
- Removing upper cover
- Removing the bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing the compressor
- Removing High pressure switch and pressure switch for control
- Removing reversing and solenoid valves coils
- Removing electronic expansion valve coil
- Removing reversing valve
- Removing Electronic expansion Valve and Solenoid Valve
- Removing electrical components
- Removing other electrical components
- Outdoor unit RAS-3HVNPE
- Servicing for Standard Series
- Outdoor Units RAS-(4-6)H(V)NCE
- Removing service cover
- Remove outlet grille
- Removing upper cover
- Removing bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing the compressor
- Removing the High pressure switch and Pressure switch for control
- Opening electrical box (P plate)
- Removing Reversing valve coil
- Removing electronic expansion valve coil
- Removing solenoid valve coil (SVA)
- Removing reversing valve
- Removing Electronic expansion valve and Solenoid valve
- Removing electrical components
- Removing other electrical components
- Outdoor Units RAS-(8-10)HNCE
- Removing service cover
- Removing air outlet grille
- Removing upper cover
- Removing the bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing the compressor
- Removing High pressure switch and pressure switch for control
- Opening electrical box (P-Mounting Plate)
- Removing reversing valve coil
- Removing electronic expansion valve coil
- Removing solenoid valve coil (SVA)
- Removing reversing valve
- Removing Electronic expansion Valve and Solenoid Valve
- Removing electrical components
- Removing other electrical components
- Outdoor Units RAS-12HNC
- Removing service cover
- Removing air outlet grille
- Removing upper cover
- Removing the bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing High pressure switch and pressure switch for control
- Opening electrical box (P-Mounting Plate)
- Removing reversing and solenoid valves coils
- Removing electronic expansion valve coil
- Removing reversing valve
- Removing Electronic expansion Valve and Solenoid Valve
- Removing electrical components
- Removing other electrical components
- Outdoor Units RAS-(4-6)H(V)NCE
- Inverter
- Thermistor
- Electronic expansion valve
- High pressure protection device
- Noise filter (NF)
- Capacitor (CB1 CB2)
- Reactor (DCL)
- Scroll compressor
- General notes
- Checking the power source and the wiring connection
- Burnt-out compressor due to an insufficient refrigerant charge
- Insufficient cooling performance when a long piping is applied
- Abnormally high operation sound (in the ceiling type indoor unit).
- Alarm code “31”
- Not cooling well due to insufficient installation space for the outdoor unit
- Maintenance work
- Service and maintenance record
- Service and maintenance record using the 7-segment display
- Service and maintenance record by remote control switch
- Pump-down method for replacing the compressor

8. Troubleshooting
187
SMGB0079 rev.0 - 01/2013
8
Phenomenon Cause Check item
Action
(Turn OFF the main switch)
The Comp. does not
stop or start even if the
setting temperature on
the LCD changes to *3)
Failure of air inlet
thermistor
Failure of thermistor
Check it by self-checking *2)
Replace or correctly connect
the wires if Abnormal Operation
exists
Disconnection of
thermistor
Abnormal operation of the remote control switch
cord
Failure of the indoor unit PCB
Check PCB by means of the
self-check mode *1)
Replace PCB if it failed
Incorrect optional setting
Check the setting condition of
“remote control thermostat” by
means of the optional setting
Setting and control:
“00”: Control by means of the
indoor thermistor for the suc-
tion air
“01”: Control by means of the
thermostat of the remote con-
trol switch
“02”: Control by means of the
average value of the indoor
thermistor for the suction air
and the thermostat of the re-
mote control switch
If the thermostat of the remote
control switch is not used, set
at “00”
Incorrect Input/Output setting
Check setting condition of “i1”
and “i2” by Input/Output setting.
* Setting and Control:
“01”: Room thermostat (Cooling)
“02”: Room thermostat (Heat-
ing)
In case that room thermostat is
not used, set for input signal ac-
tually used. If no signal is used,
set at “00”
Indoor fan speed does
not change
Failure of the Discharge
Air Temp. Thermistor
Failure of the Thermis-
tor
Check the Thermistor by
means of the self-check mode
*2)
Replace or Correctly connect
the wiring when it is abnormal
Disconnected Wire of
the Thermistor
Failure of the Remote Control Switch
Check it by means of the self-
check mode *1)
Replace if it failed
Failure of PCB for the indoor unit Replace if PCB fails
No defrost operation
mode is available dur-
ing the heating process
or the defrost operation
continues
Failure of thermistor
for outdoor evaporating
temp. during heating
Failure of thermistor
Replace or correctly connect when it is abnormal
Disconnected wire of
thermistor
Failure of 4-way valve
Disconnected 4-way
valve coil
Measure the resistance of coil
Replace the 4-way valve
Incorrect activation of
4-way valve
Enforced power supply
Disconnected control wires between indoor unit
and outdoor unit
Check the connectors Correctly connect the wiring
Failure of the outdoor
units of PCB
Disconnected wiring
to PCB
Check the connectors Correctly connect the wiring
Failure of PCB
Check PCB by means of the
self-check mode *1)
Replace PCB when the check
mode is not available
Failure of the Indoor
Unit of PCB
Disconnected wiring
to PCB
Check the connectors Correctly connect the wiring
Failure of the PCB
Check PCB by means of the
self-check mode *1)
Replace if PCB fails
The LED and the LCD
on the remote control
switch remain ON
Failure of PCB in the indoor unit or the remote
control switch