Service Manual
Table Of Contents
- Contents
- 1. General information
- 2. Unit Installation
- 3. Piping work and refrigerant charge
- 4. Electrical wiring
- 4.1 General notes
- 4.2 Electrical wiring connection for the outdoor unit
- 4.3 Setting the DIP switches for the outdoor unit
- 4.4 Common wiring
- 4.5 H-LINK II system
- 4.6 System Control
- 4.7 Electrical wiring diagrams
- 4.7.1 RAS-(2-2.5)HVNP / RAS-3HVNC (1~ 230V 50Hz)
- 4.7.2 RAS-3HVNPE (1~ 230V 50Hz)
- 4.7.3 RAS-(4-6)HVNPE (1~ 230V 50Hz)
- 4.7.4 RAS-(4-6)HNPE (3N~ 400V 50Hz)
- 4.7.5 RAS-(4-6)HVNCE (1N~ 230V 50Hz)
- 4.7.6 RAS-(4-6)HNCE (3N~ 400V 50Hz)
- 4.7.7 RAS-(8-10)HN(P/C)E (3N~ 400V 50Hz)
- 4.7.8 RAS-12HNP (3N~ 400V 50Hz) - Preliminary data
- 4.7.9 RAS-12HNC (3N~ 400V 50Hz) - Preliminary data
- 5. Control System
- 5.1 Device control system
- 5.2 Outdoor units PCB
- 5.3 Protection and safety control
- 5.4 Standard operation sequence
- 5.5 Standard control functions
- 5.5.1 Freezing protection during cooling process or dry operation
- 5.5.2 Prevention Control for High Pressure Increase during Cooling Operation
- 5.5.3 Prevention control for excessively high discharge gas temperature
- 5.5.4 Activation for protection device control
- 5.5.5 Preheating control of compressor
- 5.5.6 Prevention control for high pressure increase
- 6. Optional functions
- 7. Test run
- 7.1 Checking procedure before the test run
- 7.2 Test run procedure using the remote control switch (PC-ART)
- 7.3 Test run procedure using the remote control switch (PC-ARF)
- 7.4 Test run procedure using the wireless remote control switch (PC-LH3A/B)
- 7.5 Test run procedure from the outdoor unit side
- 7.6 Check list
- 8. Troubleshooting
- 8.1 Initial troubleshooting
- 8.2 Troubleshooting procedure
- 8.3 Troubleshooting in check mode
- 8.4 Checking procedure for main parts
- 8.4.1 Procedure for checking the DIP-IPM inverter for indoor and outdoor units
- 8.4.2 Checking capacitors CB1 & CB2.
- 8.4.3 Fault diagnosis of DC fan motor.
- 8.4.4 Checking procedure for the electronic expansion valve for indoor and outdoor units
- 8.4.5 Checking procedure for AC fan motor
- 8.4.6 Checking procedure for other parts
- 9. Spare parts
- 10. Servicing
- 10.1 Introduction
- 10.2 Servicing for Outdoor Units RAS-(2-2.5)HVNP and RAS-3HVNC
- 10.3 Servicing for Premium series
- 10.3.1 Outdoor unit RAS-3HVNPE
- 10.3.1.1 Removing service cover
- 10.3.1.2 Remove outlet grille
- 10.3.1.3 Removing upper cover
- 10.3.1.4 Removing bottom service cover and rear cover
- 10.3.1.5 Removing outdoor fan motor
- 10.3.1.6 Removing electrical box
- 10.3.1.7 Removing the compressor
- 10.3.1.8 Removing the High pressure switch and Pressure switch for control
- 10.3.1.9 Opening electrical box (P plate)
- 10.3.1.10 Removing Reversing valve coil
- 10.3.1.11 Removing electronic expansion valve coil
- 10.3.1.12 Removing solenoid valve coil (SVC)
- 10.3.1.13 Removing reversing valve
- 10.3.1.14 Removing Electronic expansion Valve and Solenoid Valve
- 10.3.1.15 Removing electrical components
- 10.3.1.16 Removing other electrical components
- 10.3.2 Outdoor units RAS-(4-6)H(V)NPE
- 10.3.2.1 Removing service cover
- 10.3.2.2 Removing air outlet grille
- 10.3.2.3 Removing upper cover
- 10.3.2.4 Removing the bottom service cover and rear cover
- 10.3.2.5 Removing outdoor fan motor
- 10.3.2.6 Removing electrical box
- 10.3.2.7 Removing the compressor
- 10.3.2.8 Removing the High pressure switch and Pressure switch for control
- 10.3.2.9 Opening electrical box (P plate)
- 10.3.2.10 Removing Reversing valve coil
- 10.3.2.11 Removing electronic expansion valve coil
- 10.3.2.12 Removing solenoid valve coil (SVA and SVC)
- 10.3.2.13 Removing reversing valve
- 10.3.2.14 Removing Electronic expansion Valve and Solenoid Valve
- 10.3.2.15 Removing electrical components
- 10.3.2.16 Removing other electrical components
- 10.3.3 Oudoor units RAS-(8-10)HNPE
- 10.3.3.1 Removing service cover
- 10.3.3.2 Removing air outlet grille
- 10.3.3.3 Removing upper cover
- 10.3.3.4 Removing the bottom service cover and rear cover
- 10.3.3.5 Removing outdoor fan motor
- 10.3.3.6 Removing electrical box
- 10.3.3.7 Removing the compressor
- 10.3.3.8 Removing High pressure switch and pressure switch for control
- 10.3.3.9 Opening electrical box (P-Mounting Plate)
- 10.3.3.10 Removing reversing valve coil
- 10.3.3.11 Removing electronic expansion valve coil
- 10.3.3.12 Removing solenoid valve coil (SVA and SVC)
- 10.3.3.13 Removing reversing valve
- 10.3.3.14 Removing Electronic expansion Valve and Solenoid Valve
- 10.3.3.15 Removing electrical components
- 10.3.3.16 Removing other electrical components
- 10.3.4 Outdoor Units RAS-12HNP
- 10.3.4.1 Removing service cover
- 10.3.4.2 Removing air outlet grille
- 10.3.4.3 Removing upper cover
- 10.3.4.4 Removing the bottom service cover and rear cover
- 10.3.4.5 Removing outdoor fan motor
- 10.3.4.6 Removing electrical box
- 10.3.4.7 Removing the compressor
- 10.3.4.8 Removing High pressure switch and pressure switch for control
- 10.3.4.9 Removing reversing and solenoid valves coils
- 10.3.4.10 Removing electronic expansion valve coil
- 10.3.4.11 Removing reversing valve
- 10.3.4.12 Removing Electronic expansion Valve and Solenoid Valve
- 10.3.4.13 Removing electrical components
- 10.3.4.14 Removing other electrical components
- 10.3.1 Outdoor unit RAS-3HVNPE
- 10.4 Servicing for Standard Series
- 10.4.1 Outdoor Units RAS-(4-6)H(V)NCE
- 10.4.1.1 Removing service cover
- 10.4.1.2 Remove outlet grille
- 10.4.1.3 Removing upper cover
- 10.4.1.4 Removing bottom service cover and rear cover
- 10.4.1.5 Removing outdoor fan motor
- 10.4.1.6 Removing electrical box
- 10.4.1.7 Removing the compressor
- 10.4.1.8 Removing the High pressure switch and Pressure switch for control
- 10.4.1.9 Opening electrical box (P plate)
- 10.4.1.10 Removing Reversing valve coil
- 10.4.1.11 Removing electronic expansion valve coil
- 10.4.1.12 Removing solenoid valve coil (SVA)
- 10.4.1.13 Removing reversing valve
- 10.4.1.14 Removing Electronic expansion valve and Solenoid valve
- 10.4.1.15 Removing electrical components
- 10.4.1.16 Removing other electrical components
- 10.4.2 Outdoor Units RAS-(8-10)HNCE
- 10.4.2.1 Removing service cover
- 10.4.2.2 Removing air outlet grille
- 10.4.2.3 Removing upper cover
- 10.4.2.4 Removing the bottom service cover and rear cover
- 10.4.2.5 Removing outdoor fan motor
- 10.4.2.6 Removing electrical box
- 10.4.2.7 Removing the compressor
- 10.4.2.8 Removing High pressure switch and pressure switch for control
- 10.4.2.9 Opening electrical box (P-Mounting Plate)
- 10.4.2.10 Removing reversing valve coil
- 10.4.2.11 Removing electronic expansion valve coil
- 10.4.2.12 Removing solenoid valve coil (SVA)
- 10.4.2.13 Removing reversing valve
- 10.4.2.14 Removing Electronic expansion Valve and Solenoid Valve
- 10.4.2.15 Removing electrical components
- 10.4.2.16 Removing other electrical components
- 10.4.3 Outdoor Units RAS-12HNC
- 10.4.3.1 Removing service cover
- 10.4.3.2 Removing air outlet grille
- 10.4.3.3 Removing upper cover
- 10.4.3.4 Removing the bottom service cover and rear cover
- 10.4.3.5 Removing outdoor fan motor
- 10.4.3.6 Removing electrical box
- 10.4.3.7 Removing High pressure switch and pressure switch for control
- 10.4.3.8 Opening electrical box (P-Mounting Plate)
- 10.4.3.9 Removing reversing and solenoid valves coils
- 10.4.3.10 Removing electronic expansion valve coil
- 10.4.3.11 Removing reversing valve
- 10.4.3.12 Removing Electronic expansion Valve and Solenoid Valve
- 10.4.3.13 Removing electrical components
- 10.4.3.14 Removing other electrical components
- 10.4.1 Outdoor Units RAS-(4-6)H(V)NCE
- 11. Electrial checks of main parts
- 12. Maintenance notes
- 12.1 General notes
- 12.1.1 Checking the power source and the wiring connection
- 12.1.2 Burnt-out compressor due to an insufficient refrigerant charge
- 12.1.3 Insufficient cooling performance when a long piping is applied
- 12.1.4 Abnormally high operation sound (in the ceiling type indoor unit).
- 12.1.5 Alarm code “31”
- 12.1.6 Not cooling well due to insufficient installation space for the outdoor unit
- 12.2 Maintenance work
- 12.3 Service and maintenance record
- 12.4 Service and maintenance record using the 7-segment display
- 12.5 Service and maintenance record by remote control switch
- 12.6 Pump-down method for replacing the compressor
- 12.1 General notes
- General information
- Safety
- Product guide
- Safety summary
- Transportation of outdoor unit
- Center of gravity
- Factory-supplied accessories for RAS-12HN(P/C)
- Installation space (Initial ckeck)
- Place provision
- Optional parts and installation
- General notes before performing pipe work
- Piping connection for outdoor unit
- Refrigerant piping range
- Refrigerant charge
- Caution in case of refrigerant leakage
- Piping work for compatibility with the piping of current installations where is used R22 or R407C.
- Drain piping
- General notes
- Electrical wiring connection for the outdoor unit
- Setting the DIP switches for the outdoor unit
- Common wiring
- H-LINK II system
- System Control
- Electrical wiring diagrams
- RAS-(2-2.5)HVNP / RAS-3HVNC (1~ 230V 50Hz)
- RAS-3HVNPE (1~ 230V 50Hz)
- RAS-(4-6)HVNPE (1~ 230V 50Hz)
- RAS-(4-6)HNPE (3N~ 400V 50Hz)
- RAS-(4-6)HVNCE (1N~ 230V 50Hz)
- RAS-(4-6)HNCE (3N~ 400V 50Hz)
- RAS-(8-10)HN(P/C)E (3N~ 400V 50Hz)
- RAS-12HNP (3N~ 400V 50Hz) - Preliminary data
- RAS-12HNC (3N~ 400V 50Hz) - Preliminary data
- Device control system
- Outdoor units PCB
- Protection and safety control
- Standard operation sequence
- Standard control functions
- Freezing protection during cooling process or dry operation
- Prevention Control for High Pressure Increase during Cooling Operation
- Prevention control for excessively high discharge gas temperature
- Activation for protection device control
- Preheating control of compressor
- Prevention control for high pressure increase
- Optional input and output signals (By 7-segment display)
- Optional functions (By 7-segment display)
- Optional functions (By remote control switch)
- Checking procedure before the test run
- Test run procedure using the remote control switch (PC-ART)
- Test run procedure using the remote control switch (PC-ARF)
- Test run procedure using the wireless remote control switch (PC-LH3A/B)
- Test run procedure from the outdoor unit side
- Check list
- Initial troubleshooting
- Troubleshooting procedure
- Troubleshooting in check mode
- Checking procedure for main parts
- RAS-(2-2.5)HVNP
- RAS-3HVNC
- RAS-3HVNPE
- RAS-(4-6)H(V)NPE
- RAS-(4-6)H(V)NCE
- RAS-(8-10)HN(P/C)E
- RAS-12HN(P/C)
- Introduction
- Servicing for Outdoor Units RAS-(2-2.5)HVNP and RAS-3HVNC
- Servicing for Premium series
- Outdoor unit RAS-3HVNPE
- Removing service cover
- Remove outlet grille
- Removing upper cover
- Removing bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing the compressor
- Removing the High pressure switch and Pressure switch for control
- Opening electrical box (P plate)
- Removing Reversing valve coil
- Removing electronic expansion valve coil
- Removing solenoid valve coil (SVC)
- Removing reversing valve
- Removing Electronic expansion Valve and Solenoid Valve
- Removing electrical components
- Removing other electrical components
- Outdoor units RAS-(4-6)H(V)NPE
- Removing service cover
- Removing air outlet grille
- Removing upper cover
- Removing the bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing the compressor
- Removing the High pressure switch and Pressure switch for control
- Opening electrical box (P plate)
- Removing Reversing valve coil
- Removing electronic expansion valve coil
- Removing solenoid valve coil (SVA and SVC)
- Removing reversing valve
- Removing Electronic expansion Valve and Solenoid Valve
- Removing electrical components
- Removing other electrical components
- Oudoor units RAS-(8-10)HNPE
- Removing service cover
- Removing air outlet grille
- Removing upper cover
- Removing the bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing the compressor
- Removing High pressure switch and pressure switch for control
- Opening electrical box (P-Mounting Plate)
- Removing reversing valve coil
- Removing electronic expansion valve coil
- Removing solenoid valve coil (SVA and SVC)
- Removing reversing valve
- Removing Electronic expansion Valve and Solenoid Valve
- Removing electrical components
- Removing other electrical components
- Outdoor Units RAS-12HNP
- Removing service cover
- Removing air outlet grille
- Removing upper cover
- Removing the bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing the compressor
- Removing High pressure switch and pressure switch for control
- Removing reversing and solenoid valves coils
- Removing electronic expansion valve coil
- Removing reversing valve
- Removing Electronic expansion Valve and Solenoid Valve
- Removing electrical components
- Removing other electrical components
- Outdoor unit RAS-3HVNPE
- Servicing for Standard Series
- Outdoor Units RAS-(4-6)H(V)NCE
- Removing service cover
- Remove outlet grille
- Removing upper cover
- Removing bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing the compressor
- Removing the High pressure switch and Pressure switch for control
- Opening electrical box (P plate)
- Removing Reversing valve coil
- Removing electronic expansion valve coil
- Removing solenoid valve coil (SVA)
- Removing reversing valve
- Removing Electronic expansion valve and Solenoid valve
- Removing electrical components
- Removing other electrical components
- Outdoor Units RAS-(8-10)HNCE
- Removing service cover
- Removing air outlet grille
- Removing upper cover
- Removing the bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing the compressor
- Removing High pressure switch and pressure switch for control
- Opening electrical box (P-Mounting Plate)
- Removing reversing valve coil
- Removing electronic expansion valve coil
- Removing solenoid valve coil (SVA)
- Removing reversing valve
- Removing Electronic expansion Valve and Solenoid Valve
- Removing electrical components
- Removing other electrical components
- Outdoor Units RAS-12HNC
- Removing service cover
- Removing air outlet grille
- Removing upper cover
- Removing the bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing High pressure switch and pressure switch for control
- Opening electrical box (P-Mounting Plate)
- Removing reversing and solenoid valves coils
- Removing electronic expansion valve coil
- Removing reversing valve
- Removing Electronic expansion Valve and Solenoid Valve
- Removing electrical components
- Removing other electrical components
- Outdoor Units RAS-(4-6)H(V)NCE
- Inverter
- Thermistor
- Electronic expansion valve
- High pressure protection device
- Noise filter (NF)
- Capacitor (CB1 CB2)
- Reactor (DCL)
- Scroll compressor
- General notes
- Checking the power source and the wiring connection
- Burnt-out compressor due to an insufficient refrigerant charge
- Insufficient cooling performance when a long piping is applied
- Abnormally high operation sound (in the ceiling type indoor unit).
- Alarm code “31”
- Not cooling well due to insufficient installation space for the outdoor unit
- Maintenance work
- Service and maintenance record
- Service and maintenance record using the 7-segment display
- Service and maintenance record by remote control switch
- Pump-down method for replacing the compressor

7. Test run
177
SMGB0079 rev.0 - 01/2013
7
7.5 Test run procedure from the outdoor unit side
The test run procedure from the outdoor unit side is shown below.
You can set this DIP switch while the power source is ON.
Setting of dip switch
DSW1
1 Test Run
2 COOL/HEAT
(Setting ON: Heat Operation)
3 COOL / HEAT intermediate season
4 Manual Compressor stop
D A N G E R
• DonottouchanyotherelectricalcomponentswhileyouaresettingtheswitchesonthePCB.
• DonotattachordetachtheserviceaccesspanelwhenthepowersourcefortheoutdoorunitisONandthe
outdoorunitisoperating.
• SetalltheDIPswitchesofDSW1toOFFaftercompletingthetestrun.
Operation Dip Switch Setting Operation Remarks
Test Run
Setting of Operation Mode:
Cooling: Set DSW1-2 OFF.
Heating: Set DSW1-2 ON.
Starting Test Run:
Set DSW1-1 ON and the ope-
ration is started after a few ~20
seconds.
Cooling Heating
The indoor unit automatically start to
operate when the test run of the outdoor
unit is set.
The ON/OFF operation can be per-
formed from the remote control switch or
DSW1-1 of the outdoor unit.
Continuous operation during 2 hours
is performed without Thermo-OFF.
N O T E
• TEST RUN operation time can be
increased depressing the time
switch in the Remote Control.
• If is setting DSW1-3 ON, cooling/
heating intermediate season
mode is activaded.
• Take care that the indoor units start
operation in accord with the test run
operation of the outdoor unit.
• The test run is started from the outdo-
or unit and stopped from the remote
control switch, the test run function
of the remote control switch is cance-
lled. However, the test run function of
the outdoor unit is not cancelled
• In case that the plural indoor units
are connected with one remote con-
trol switch, all the units start test run
operation at the same time, therefore,
turn the power source OFF for the in-
door units not to operate test run. In
this case, the “TEST RUN” indication
of the remote control switch may ic-
ker, and this is not abnormal.
• The setting of DSW1 is not required
for the test run from the remote con-
trol switch.
Manual
OFF of
Compressor
Setting:
Compressor Manual OFF:
Set DSW1-4 ON.
Compressor ON:
Set DSW1-4 OFF.
When DSW1-4 is ON during com-
pressor operation, the compressor stops
to operate immediately and the indoor
unit is under the condition of Thermo-
OFF.
When DSW1-4 is OFF, the com-
pressor starts to operate after the can-
cellation of 3-minutes guard.
• Do not repeat compressor ON/OFF
frequently.