6
Slo defrost setting (bJ)
Press “PSW1” and select the setting condition “1” at the slow defrost setting “bJ“.
Indoor fan operation is stopped during the defrost operation.
Setting condition* Indoor fan operation
0 Indoor fan stop during defrost operation
1 Indoor fan SLo during defrost operation
Cancellation of outdoor hot start limit (H)
Press “PSW1” and select the setting condition “1” at the cancellation of hot start setting H”, so the hot start protection
control can be canceled.
Long piping setting (nU)
Press “PSW1” and select the setting condition “1” at the long piping setting “nU”.
If cooling capacity or heating capacity is not enough under the long-distance piping condition, this function can be set the
target compressor frequency higher than normal target value.
Wave function setting (UE)
Press “PSW1” and select the setting condition “1”, so that the wave function setting “UE”.
While this function is activated, the maximum limit of running current is changed from 60% to 100% as shown in the gure.
Electricity
consumption
(100%)
Electricity
consumption
(60 to 80%)
N O T E
• Wavefunctioncanbeactivatedwhendemandfunctionisselectedatoneoftheinputterminalindicationsi1,i2
andi3.
• Theminimumlimitofrunningcurrentcontrolisaccordingtothesetvalueofthedemandfunction.
• Ifdemandfunctionisnotsetattheinputterminalindication,thisfunctioncannotbeactivated.