Service Manual
Table Of Contents
- Contents
- 1. General information
- 2. Unit Installation
- 3. Piping work and refrigerant charge
- 4. Electrical wiring
- 4.1 General notes
- 4.2 Electrical wiring connection for the outdoor unit
- 4.3 Setting the DIP switches for the outdoor unit
- 4.4 Common wiring
- 4.5 H-LINK II system
- 4.6 System Control
- 4.7 Electrical wiring diagrams
- 4.7.1 RAS-(2-2.5)HVNP / RAS-3HVNC (1~ 230V 50Hz)
- 4.7.2 RAS-3HVNPE (1~ 230V 50Hz)
- 4.7.3 RAS-(4-6)HVNPE (1~ 230V 50Hz)
- 4.7.4 RAS-(4-6)HNPE (3N~ 400V 50Hz)
- 4.7.5 RAS-(4-6)HVNCE (1N~ 230V 50Hz)
- 4.7.6 RAS-(4-6)HNCE (3N~ 400V 50Hz)
- 4.7.7 RAS-(8-10)HN(P/C)E (3N~ 400V 50Hz)
- 4.7.8 RAS-12HNP (3N~ 400V 50Hz) - Preliminary data
- 4.7.9 RAS-12HNC (3N~ 400V 50Hz) - Preliminary data
- 5. Control System
- 5.1 Device control system
- 5.2 Outdoor units PCB
- 5.3 Protection and safety control
- 5.4 Standard operation sequence
- 5.5 Standard control functions
- 5.5.1 Freezing protection during cooling process or dry operation
- 5.5.2 Prevention Control for High Pressure Increase during Cooling Operation
- 5.5.3 Prevention control for excessively high discharge gas temperature
- 5.5.4 Activation for protection device control
- 5.5.5 Preheating control of compressor
- 5.5.6 Prevention control for high pressure increase
- 6. Optional functions
- 7. Test run
- 7.1 Checking procedure before the test run
- 7.2 Test run procedure using the remote control switch (PC-ART)
- 7.3 Test run procedure using the remote control switch (PC-ARF)
- 7.4 Test run procedure using the wireless remote control switch (PC-LH3A/B)
- 7.5 Test run procedure from the outdoor unit side
- 7.6 Check list
- 8. Troubleshooting
- 8.1 Initial troubleshooting
- 8.2 Troubleshooting procedure
- 8.3 Troubleshooting in check mode
- 8.4 Checking procedure for main parts
- 8.4.1 Procedure for checking the DIP-IPM inverter for indoor and outdoor units
- 8.4.2 Checking capacitors CB1 & CB2.
- 8.4.3 Fault diagnosis of DC fan motor.
- 8.4.4 Checking procedure for the electronic expansion valve for indoor and outdoor units
- 8.4.5 Checking procedure for AC fan motor
- 8.4.6 Checking procedure for other parts
- 9. Spare parts
- 10. Servicing
- 10.1 Introduction
- 10.2 Servicing for Outdoor Units RAS-(2-2.5)HVNP and RAS-3HVNC
- 10.3 Servicing for Premium series
- 10.3.1 Outdoor unit RAS-3HVNPE
- 10.3.1.1 Removing service cover
- 10.3.1.2 Remove outlet grille
- 10.3.1.3 Removing upper cover
- 10.3.1.4 Removing bottom service cover and rear cover
- 10.3.1.5 Removing outdoor fan motor
- 10.3.1.6 Removing electrical box
- 10.3.1.7 Removing the compressor
- 10.3.1.8 Removing the High pressure switch and Pressure switch for control
- 10.3.1.9 Opening electrical box (P plate)
- 10.3.1.10 Removing Reversing valve coil
- 10.3.1.11 Removing electronic expansion valve coil
- 10.3.1.12 Removing solenoid valve coil (SVC)
- 10.3.1.13 Removing reversing valve
- 10.3.1.14 Removing Electronic expansion Valve and Solenoid Valve
- 10.3.1.15 Removing electrical components
- 10.3.1.16 Removing other electrical components
- 10.3.2 Outdoor units RAS-(4-6)H(V)NPE
- 10.3.2.1 Removing service cover
- 10.3.2.2 Removing air outlet grille
- 10.3.2.3 Removing upper cover
- 10.3.2.4 Removing the bottom service cover and rear cover
- 10.3.2.5 Removing outdoor fan motor
- 10.3.2.6 Removing electrical box
- 10.3.2.7 Removing the compressor
- 10.3.2.8 Removing the High pressure switch and Pressure switch for control
- 10.3.2.9 Opening electrical box (P plate)
- 10.3.2.10 Removing Reversing valve coil
- 10.3.2.11 Removing electronic expansion valve coil
- 10.3.2.12 Removing solenoid valve coil (SVA and SVC)
- 10.3.2.13 Removing reversing valve
- 10.3.2.14 Removing Electronic expansion Valve and Solenoid Valve
- 10.3.2.15 Removing electrical components
- 10.3.2.16 Removing other electrical components
- 10.3.3 Oudoor units RAS-(8-10)HNPE
- 10.3.3.1 Removing service cover
- 10.3.3.2 Removing air outlet grille
- 10.3.3.3 Removing upper cover
- 10.3.3.4 Removing the bottom service cover and rear cover
- 10.3.3.5 Removing outdoor fan motor
- 10.3.3.6 Removing electrical box
- 10.3.3.7 Removing the compressor
- 10.3.3.8 Removing High pressure switch and pressure switch for control
- 10.3.3.9 Opening electrical box (P-Mounting Plate)
- 10.3.3.10 Removing reversing valve coil
- 10.3.3.11 Removing electronic expansion valve coil
- 10.3.3.12 Removing solenoid valve coil (SVA and SVC)
- 10.3.3.13 Removing reversing valve
- 10.3.3.14 Removing Electronic expansion Valve and Solenoid Valve
- 10.3.3.15 Removing electrical components
- 10.3.3.16 Removing other electrical components
- 10.3.4 Outdoor Units RAS-12HNP
- 10.3.4.1 Removing service cover
- 10.3.4.2 Removing air outlet grille
- 10.3.4.3 Removing upper cover
- 10.3.4.4 Removing the bottom service cover and rear cover
- 10.3.4.5 Removing outdoor fan motor
- 10.3.4.6 Removing electrical box
- 10.3.4.7 Removing the compressor
- 10.3.4.8 Removing High pressure switch and pressure switch for control
- 10.3.4.9 Removing reversing and solenoid valves coils
- 10.3.4.10 Removing electronic expansion valve coil
- 10.3.4.11 Removing reversing valve
- 10.3.4.12 Removing Electronic expansion Valve and Solenoid Valve
- 10.3.4.13 Removing electrical components
- 10.3.4.14 Removing other electrical components
- 10.3.1 Outdoor unit RAS-3HVNPE
- 10.4 Servicing for Standard Series
- 10.4.1 Outdoor Units RAS-(4-6)H(V)NCE
- 10.4.1.1 Removing service cover
- 10.4.1.2 Remove outlet grille
- 10.4.1.3 Removing upper cover
- 10.4.1.4 Removing bottom service cover and rear cover
- 10.4.1.5 Removing outdoor fan motor
- 10.4.1.6 Removing electrical box
- 10.4.1.7 Removing the compressor
- 10.4.1.8 Removing the High pressure switch and Pressure switch for control
- 10.4.1.9 Opening electrical box (P plate)
- 10.4.1.10 Removing Reversing valve coil
- 10.4.1.11 Removing electronic expansion valve coil
- 10.4.1.12 Removing solenoid valve coil (SVA)
- 10.4.1.13 Removing reversing valve
- 10.4.1.14 Removing Electronic expansion valve and Solenoid valve
- 10.4.1.15 Removing electrical components
- 10.4.1.16 Removing other electrical components
- 10.4.2 Outdoor Units RAS-(8-10)HNCE
- 10.4.2.1 Removing service cover
- 10.4.2.2 Removing air outlet grille
- 10.4.2.3 Removing upper cover
- 10.4.2.4 Removing the bottom service cover and rear cover
- 10.4.2.5 Removing outdoor fan motor
- 10.4.2.6 Removing electrical box
- 10.4.2.7 Removing the compressor
- 10.4.2.8 Removing High pressure switch and pressure switch for control
- 10.4.2.9 Opening electrical box (P-Mounting Plate)
- 10.4.2.10 Removing reversing valve coil
- 10.4.2.11 Removing electronic expansion valve coil
- 10.4.2.12 Removing solenoid valve coil (SVA)
- 10.4.2.13 Removing reversing valve
- 10.4.2.14 Removing Electronic expansion Valve and Solenoid Valve
- 10.4.2.15 Removing electrical components
- 10.4.2.16 Removing other electrical components
- 10.4.3 Outdoor Units RAS-12HNC
- 10.4.3.1 Removing service cover
- 10.4.3.2 Removing air outlet grille
- 10.4.3.3 Removing upper cover
- 10.4.3.4 Removing the bottom service cover and rear cover
- 10.4.3.5 Removing outdoor fan motor
- 10.4.3.6 Removing electrical box
- 10.4.3.7 Removing High pressure switch and pressure switch for control
- 10.4.3.8 Opening electrical box (P-Mounting Plate)
- 10.4.3.9 Removing reversing and solenoid valves coils
- 10.4.3.10 Removing electronic expansion valve coil
- 10.4.3.11 Removing reversing valve
- 10.4.3.12 Removing Electronic expansion Valve and Solenoid Valve
- 10.4.3.13 Removing electrical components
- 10.4.3.14 Removing other electrical components
- 10.4.1 Outdoor Units RAS-(4-6)H(V)NCE
- 11. Electrial checks of main parts
- 12. Maintenance notes
- 12.1 General notes
- 12.1.1 Checking the power source and the wiring connection
- 12.1.2 Burnt-out compressor due to an insufficient refrigerant charge
- 12.1.3 Insufficient cooling performance when a long piping is applied
- 12.1.4 Abnormally high operation sound (in the ceiling type indoor unit).
- 12.1.5 Alarm code “31”
- 12.1.6 Not cooling well due to insufficient installation space for the outdoor unit
- 12.2 Maintenance work
- 12.3 Service and maintenance record
- 12.4 Service and maintenance record using the 7-segment display
- 12.5 Service and maintenance record by remote control switch
- 12.6 Pump-down method for replacing the compressor
- 12.1 General notes
- General information
- Safety
- Product guide
- Safety summary
- Transportation of outdoor unit
- Center of gravity
- Factory-supplied accessories for RAS-12HN(P/C)
- Installation space (Initial ckeck)
- Place provision
- Optional parts and installation
- General notes before performing pipe work
- Piping connection for outdoor unit
- Refrigerant piping range
- Refrigerant charge
- Caution in case of refrigerant leakage
- Piping work for compatibility with the piping of current installations where is used R22 or R407C.
- Drain piping
- General notes
- Electrical wiring connection for the outdoor unit
- Setting the DIP switches for the outdoor unit
- Common wiring
- H-LINK II system
- System Control
- Electrical wiring diagrams
- RAS-(2-2.5)HVNP / RAS-3HVNC (1~ 230V 50Hz)
- RAS-3HVNPE (1~ 230V 50Hz)
- RAS-(4-6)HVNPE (1~ 230V 50Hz)
- RAS-(4-6)HNPE (3N~ 400V 50Hz)
- RAS-(4-6)HVNCE (1N~ 230V 50Hz)
- RAS-(4-6)HNCE (3N~ 400V 50Hz)
- RAS-(8-10)HN(P/C)E (3N~ 400V 50Hz)
- RAS-12HNP (3N~ 400V 50Hz) - Preliminary data
- RAS-12HNC (3N~ 400V 50Hz) - Preliminary data
- Device control system
- Outdoor units PCB
- Protection and safety control
- Standard operation sequence
- Standard control functions
- Freezing protection during cooling process or dry operation
- Prevention Control for High Pressure Increase during Cooling Operation
- Prevention control for excessively high discharge gas temperature
- Activation for protection device control
- Preheating control of compressor
- Prevention control for high pressure increase
- Optional input and output signals (By 7-segment display)
- Optional functions (By 7-segment display)
- Optional functions (By remote control switch)
- Checking procedure before the test run
- Test run procedure using the remote control switch (PC-ART)
- Test run procedure using the remote control switch (PC-ARF)
- Test run procedure using the wireless remote control switch (PC-LH3A/B)
- Test run procedure from the outdoor unit side
- Check list
- Initial troubleshooting
- Troubleshooting procedure
- Troubleshooting in check mode
- Checking procedure for main parts
- RAS-(2-2.5)HVNP
- RAS-3HVNC
- RAS-3HVNPE
- RAS-(4-6)H(V)NPE
- RAS-(4-6)H(V)NCE
- RAS-(8-10)HN(P/C)E
- RAS-12HN(P/C)
- Introduction
- Servicing for Outdoor Units RAS-(2-2.5)HVNP and RAS-3HVNC
- Servicing for Premium series
- Outdoor unit RAS-3HVNPE
- Removing service cover
- Remove outlet grille
- Removing upper cover
- Removing bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing the compressor
- Removing the High pressure switch and Pressure switch for control
- Opening electrical box (P plate)
- Removing Reversing valve coil
- Removing electronic expansion valve coil
- Removing solenoid valve coil (SVC)
- Removing reversing valve
- Removing Electronic expansion Valve and Solenoid Valve
- Removing electrical components
- Removing other electrical components
- Outdoor units RAS-(4-6)H(V)NPE
- Removing service cover
- Removing air outlet grille
- Removing upper cover
- Removing the bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing the compressor
- Removing the High pressure switch and Pressure switch for control
- Opening electrical box (P plate)
- Removing Reversing valve coil
- Removing electronic expansion valve coil
- Removing solenoid valve coil (SVA and SVC)
- Removing reversing valve
- Removing Electronic expansion Valve and Solenoid Valve
- Removing electrical components
- Removing other electrical components
- Oudoor units RAS-(8-10)HNPE
- Removing service cover
- Removing air outlet grille
- Removing upper cover
- Removing the bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing the compressor
- Removing High pressure switch and pressure switch for control
- Opening electrical box (P-Mounting Plate)
- Removing reversing valve coil
- Removing electronic expansion valve coil
- Removing solenoid valve coil (SVA and SVC)
- Removing reversing valve
- Removing Electronic expansion Valve and Solenoid Valve
- Removing electrical components
- Removing other electrical components
- Outdoor Units RAS-12HNP
- Removing service cover
- Removing air outlet grille
- Removing upper cover
- Removing the bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing the compressor
- Removing High pressure switch and pressure switch for control
- Removing reversing and solenoid valves coils
- Removing electronic expansion valve coil
- Removing reversing valve
- Removing Electronic expansion Valve and Solenoid Valve
- Removing electrical components
- Removing other electrical components
- Outdoor unit RAS-3HVNPE
- Servicing for Standard Series
- Outdoor Units RAS-(4-6)H(V)NCE
- Removing service cover
- Remove outlet grille
- Removing upper cover
- Removing bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing the compressor
- Removing the High pressure switch and Pressure switch for control
- Opening electrical box (P plate)
- Removing Reversing valve coil
- Removing electronic expansion valve coil
- Removing solenoid valve coil (SVA)
- Removing reversing valve
- Removing Electronic expansion valve and Solenoid valve
- Removing electrical components
- Removing other electrical components
- Outdoor Units RAS-(8-10)HNCE
- Removing service cover
- Removing air outlet grille
- Removing upper cover
- Removing the bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing the compressor
- Removing High pressure switch and pressure switch for control
- Opening electrical box (P-Mounting Plate)
- Removing reversing valve coil
- Removing electronic expansion valve coil
- Removing solenoid valve coil (SVA)
- Removing reversing valve
- Removing Electronic expansion Valve and Solenoid Valve
- Removing electrical components
- Removing other electrical components
- Outdoor Units RAS-12HNC
- Removing service cover
- Removing air outlet grille
- Removing upper cover
- Removing the bottom service cover and rear cover
- Removing outdoor fan motor
- Removing electrical box
- Removing High pressure switch and pressure switch for control
- Opening electrical box (P-Mounting Plate)
- Removing reversing and solenoid valves coils
- Removing electronic expansion valve coil
- Removing reversing valve
- Removing Electronic expansion Valve and Solenoid Valve
- Removing electrical components
- Removing other electrical components
- Outdoor Units RAS-(4-6)H(V)NCE
- Inverter
- Thermistor
- Electronic expansion valve
- High pressure protection device
- Noise filter (NF)
- Capacitor (CB1 CB2)
- Reactor (DCL)
- Scroll compressor
- General notes
- Checking the power source and the wiring connection
- Burnt-out compressor due to an insufficient refrigerant charge
- Insufficient cooling performance when a long piping is applied
- Abnormally high operation sound (in the ceiling type indoor unit).
- Alarm code “31”
- Not cooling well due to insufficient installation space for the outdoor unit
- Maintenance work
- Service and maintenance record
- Service and maintenance record using the 7-segment display
- Service and maintenance record by remote control switch
- Pump-down method for replacing the compressor

5. Control System
119
SMGB0079 rev.0 - 01/2013
5
The gure below shows the outline of the control system
Transmission
circuit
Remote
control MCU
Wireless remote control switch
Wireless transmission circuit
A+D conversion
circuit
Thermistor for inlet air
Thermistor of discharge air
Thermistor for gas pipe
Thermistor for liquid pipe
A+D conversion
circuit
Suction gas pressure sensor
Discharge gas pressure sensor
Thermistor for outdoor temperature
Discharge gas thermistor
Thermistor for heating evaporation temp.
Protection circuit
Inverter control
MCU
Inverter power
section
MC
CT1
Outdoor unit MCU
Inverter control
for fan MCU
Relay drive
circuit
Electrical control
expansion valve
drive circuit
Transmission
circuit
Transmission
circuit
Protection
circuit
Fan control
Indoor unit MCU
Transmission
circuit
Relay drive
circuit
Electrical control
expansion valve drive
circuit
Remote
control MCU
Remote control switch
CH1
MV
MOF1
RVR
SVA
B.F.
MOF2
MV MS MIF
Indoor unit Outdoor unit
Multiple signals
Single signals
Operation signals
To the transmission of the
next indoor unit or the next
outdoor unit (H-Link)
PSC
Power source
(*)
Symbol Name Symbol Name
MC Motor (for compressor) CH Crankcase heater
MIF Motor (for indoor fan) CT1 Current transformer
MOF1, 2 Motor (for outdoor fan) RVR 4-Way valve
MS Motor (for auto-louver) SVA,B,F Solenoid valve
MV Electronic expansion valve PSC Pressure switch for control
CMC Compressor magnetic contactor EHW Electric heater
(*) For RAS-12HN(P/C) models. Other than this, the two fan motors are controlled by the Inverter.