4. Electrical wiring
98
SMGB0079 rev.0 - 01/2013
4.4 Common wiring
4.4.1  Electrical wiring between outdoor and indoor unit
Connect the electrical wires between the indoor unit and the outdoor unit as show in the gure.
When installing the electrical wiring, follow local codes and regulations.
The refrigerant piping and the control wiring are connected to the units in the same refrigerant cycle.
Use twist pair wire (more than 0.75 mm
2
) for operation wiring between the outdoor unit and indoor unit, and operation
wiring between indoor unit and indoor unit.
Use a 2-core wire for the operating line (do not use wire with more than 3 cores).
Use shielded wires for intermediate wiring to protect the units from noise interference at lengths of less than 300 m.
The size must comply with local code.
Open a hole near the connection hole of power source wiring when multiple outdoor units are connected from a single
power source line.
The recommended breaker sizes are detailed in the Wire size section.
In the case that a conduit tube for eld-wiring is not used, x rubber bushes with adhesive on the panel.
All eld wiring and equipment must comply with local and international codes.
H-LINK twist pair shielded cable must be grounded in the outdoor unit side.
C A U T I O N
Takecarewiththeconnectionoftheoperatingline.IncorrectconnectionmaycauseafailureofthePCB.
Power source from the outdoor unit to the indoor unit Independent power source of outdoor unit and indoor unit
3
3
3
L1 L2 L3 NL1 L2 L3 N
L1 L2 L3 N
No. 0 System
Outdoor unit
No. 0 System
Outdoor unit
Operating Line
(Shielded Pair Cable)
DC5V (Non-Pole Transmission,
H-LINK System)
Remote Control Switch
(Twisted Shielded Pair
Cable)
Operating Line
(Twisted Shielded Pair
Cable)
DC5V (Non-Pole
Transmission, H-LINK
System)
Indoor Unit
Indoor Unit
Terminal board
Circuit Breaker
Earthleakage Breaker
Field Wiring
Field supplied
Optional Accessory
Remote Control Switch
(Twisted Shielded Pair
Cable)
Indoor Unit
Indoor Unit