Instruction Manual

Table Of Contents
Input and Output Number Display and Connectors
Input Number Display
Port
Factory Setting
Setting
Input/Output Indication Setting Item Indication
Input 1 CN3 1-2 Remote ON/OFF 1 (Level) 03
Input 2 CN3 2-3 Prohibiting Remote Control after Manual Stoppage 06
Output 1 CN7 1-2 Operation 01
Output 2 CN7 1-3 Alarm 02
Output 3 CN8 1-2 Thermo-ON for Heating 06
Input and Output Settings and Display Codes
Code Indicated Input Code Indicated Output
00 Not set 00 Not set
01 Room Thermostat (for Cooling) 01 Operation
02 Room Thermostat (for Heating) 02 Alarm
03 Remote ON/OFF 1 (Level) 03 Cooling
04 Remote ON/OFF 2 (Operation) 04 Thermo-ON for Cooling
05 Remote ON/OFF 2 (Stoppage) 05 Heating
06 Forbidding Remote Control after Manual Stoppage 06 Thermo-ON for Heating
07 Remote Cooling / Heating Change 07 Not set
09 Setback Operation
? NOTE
Change the optional setting after waiting at least three minutes elapsed time after start-up.
Do not set the elevating grille for the total heat exchanger.
Record the setting conditions for each input and output in the “Setting” column of the table.
SERVICE & INSTALLATION MENU