Instruction Manual
Table Of Contents
- 1 Safety summary
- 2 Switch Names and Functions
- 3 Operation
- 4 Icon Description
- 5 Function Menu
- 5.1 Simple Timer Setting
- 5.2 Operation Schedule Setting
- 5.3 Power Savings Setting
- 5.4 Night Quiet Operation
- 5.5 Power Saving/Night Quiet Schedule Setting
- 5.6 Power Consumption Display
- 5.7 Autoboost (QUICK MODE) Setting
- 5.8 Comfort Setting
- 5.9 Motion sensor setting
- 5.10 Setback Setting
- 5.11 Elevating Grille
- 5.12 Filter Reminder Reset Setting
- 5.13 FrostWash
- 5.14 Individual Louver Setting
- 5.15 Cancel Individual Louver Setting
- 5.16 Louver Open/Close
- 5.17 Ventilation
- 5.18 Total Heat Exchanger Setting
- 6 Service & installation menu
- 6.1 Installation menu
- 6.1.1 Test Run
- 6.1.2 Function selection
- 6.1.3 Thermistor Selection
- 6.1.4 Input / Output Setting
- 6.1.5 Thermistor Calibration in Controller
- 6.1.6 Fan Speed at Cooling Thermo-OFF
- 6.1.7 Fan Speed at Heating Thermo-OFF
- 6.1.8 Indoor Unit Address Change
- 6.1.9 Address Check Operation
- 6.1.10 Address Initialization
- 6.1.11 Setting Initialization
- 6.1.12 Main Remote Setting
- 6.1.13 Priority Setting
- 6.1.14 Cancel Preheating Control
- 6.1.15 Elevating grille Setting
- 6.1.16 Power Up Setting
- 6.1.17 Setback Trigger Unit
- 6.1.18 Refrigerant Leak Sensor Setting
- 6.2 Service menu
- 6.3 Check Menu
- 6.1 Installation menu
- 7 Screen Display Setting menu
- 8 Contact Information menu
- 9 Hotel Mode Setting
- 10 In Alarm Condition
Input and Output Number Display and Connectors
Input Number Display
Port
Factory Setting
Setting
Input/Output Indication Setting Item Indication
Input 1 CN3 1-2 Remote ON/OFF 1 (Level) 03
Input 2 CN3 2-3 Prohibiting Remote Control after Manual Stoppage 06
Output 1 CN7 1-2 Operation 01
Output 2 CN7 1-3 Alarm 02
Output 3 CN8 1-2 Thermo-ON for Heating 06
Input and Output Settings and Display Codes
Code Indicated Input Code Indicated Output
00 Not set 00 Not set
01 Room Thermostat (for Cooling) 01 Operation
02 Room Thermostat (for Heating) 02 Alarm
03 Remote ON/OFF 1 (Level) 03 Cooling
04 Remote ON/OFF 2 (Operation) 04 Thermo-ON for Cooling
05 Remote ON/OFF 2 (Stoppage) 05 Heating
06 Forbidding Remote Control after Manual Stoppage 06 Thermo-ON for Heating
07 Remote Cooling / Heating Change 07 Not set
09 Setback Operation
? NOTE
• Change the optional setting after waiting at least three minutes elapsed time after start-up.
• Do not set the elevating grille for the total heat exchanger.
• Record the setting conditions for each input and output in the “Setting” column of the table.
SERVICE & INSTALLATION MENU
PMML0565 rev.1 - 04/202260