Element Optional function
Individual
setting
Settings Setting conditions Description
q8 Not used -
00
- Use at 00 conditions
01
q9 Not used -
00
- Use at 00 conditions
01
qA Not used -
00
- Use at 00 conditions
01
qb Operation mode with setback X
00 Disabled
Operation modes in which
setback operation is activated to
keep a minimum comfort in the
room while it is not occupied.
01 Cooling
02 Heating
03 Cooling/Heating
qC
Temperature differential for
the setback function
X
00 2.0°C
Target temperatures for both
cooling and heating operation
are determined versus a
temperature to start setback
operation (rE, rF)
Target temperature calculation:
Target temperature in cooling
mode: rF - qC (°C)
Target temperature in heating
mode: rE + qC (°C)
01 3.0°C
02 4.0°C
03 5.0°C
04 1.0°C
qd
Minimum stop time of
setback
X
00 10 minutes
To avoid the frequent activation
of setback operation, a
minimum off-time shall pass
from the end of setback
operation until the beginning of
the following setback operation.
Even if room temperature
reaches the setpoint to start
setback operation, setback
operation does not start until the
minimum off-time has expired.
01 20 minutes
02 30 minutes
03 40 minutes
04 50 minutes
05 60 minutes
06 70 minutes
07 80 minutes
08 90 minutes
09 100 minutes
10 110 minutes
11 120 minutes
qE Setback mode X
00 Always
When selecting “01: Input”,
it is necessary to set up one
input contact (i1 or i2) with
the setback function “09”. This
operation has to be done in the
input/output setting menu of the
remote controller.
When selecting “02: Schedule”
or “03: Manual”, additional
settings are required.
01 Input
02 Schedule
03 Manual
qF
Operation state after the end
of setback operation
X
00 Stop
Operation state to switch
to upon the end of setback
duration.
01 Run
02
Operation state before the beginning of
setback
r1 Dual setpoint X
00 Function disabled (factory setting)
This function allows the setting
of independent setpoints for
cooling and heating in the
automatic cooling/heating mode.
01 Function enabled