Element Optional function
Individual
setting
Settings Setting conditions Description
P1
Setting temperature in 0.5°C
steps
X
00
Enabled (0.5°C steps)
(factory setting)
This function is used to dene
whether setting temperature is
adjusted in 0.5°C steps (when
set to “00”) or in 1°C steps
(when set to “01”).
This setting also determines
whether the resolution of
temperature differential of the
thermistor is 0.5°C (when set to
00”) or 1°C (when set to “01”).
01 Disabled (1°C steps)
P2 Not used -
00
- Use at 00 conditions
01
P3
Temperature sensor
displayed
X
00 Inlet air thermistor (Tin)
This function is used to
select the thermistor whose
temperature is shown when
function P4 is set to 01.
01 Outdoor air thermistor (Tout)
02 Remote controller sensor (RCS)
03
Remote temperature sensor (connected
to THM4 on indoor unit main PCB)
(THM4)
P4
Display of sensor
temperature
X
00 Hidden
This function is used to display
the temperature of the sensor
selected with function P3.
01 Shown
P5
Display of setting
temperature when operation
mode is Fan
X
00 Shown
This function is used to hide the
display of setting temperature
during operation in fan mode.
01 Hidden
P6 Not available
“- -”
permanent
P7
Prohibition of menu screen
transition
X
00 Function disabled (factory setting)
This function is used to prohibit
the access to the menu screens.
The text "Display disabled"
appears on screen instead.
01 Function enabled
P8
Display of Maintenance
Explanation
X
00 Available
This function is used to display
the maintenance explanation on
the screen when a maintenance
sign is shown.
01 Not Available
P9 Display of Alarm Explanation X
00 Available
This function is used to display
the alarm explanation on the
screen when an alarm occurs.
01 Not Available
PA Daylight saving time X
00 1 hour
This function is used to set the
amount of adjustment when
daylight saving time is applied.
01 2 hours
Pb Not used -
00
- Use at 00 conditions
01
PC Not used -
00
- Use at 00 conditions
01
q1 Not used -
00
- Use at 00 conditions
01
q2 Not used - - - Not used
q3 Not used - - - Not used
q4 Not used - - - Not used
q5 Not used - - - Not used
q6 Not used -
00
- Use at 00 conditions
01
q7 Not used -
00
- Use at 00 conditions
01
EN
SERVICE & INSTALLATION MENU