Element Optional function
Individual
setting
Settings Setting conditions Description
Jc
Calibration of remote
controller sensor
X
00 -0°C
Offset for the remote controller
sensor
01 -0.5°C
02 -1.0°C
03 -1.5°C
04 -2.0°C
05 -2.5°C
06 -3.0°C
07 -3.5°C
08 +0.5°C
09 +1.0°C
10 +1.5°C
11 +2.0°C
12 +2.5°C
13 +3.0°C
14 +3.5°C
15 -0°C
K1 Not used -
00
- Use at 00 conditions
01
K2 Not used -
00
- Use at 00 conditions
01
K3 Not used -
00
- Use at 00 conditions
01
K4 Not used -
00
- Use at 00 conditions
01
02
03
K5
Detection level of the motion
sensor kit
O
00 Standard (factory setting)
Models:
RPF(I)-FSN2E
Not available, use at 00
conditions.
This parameter denes the
sensitiveness of the motion
sensor. The amount of activity in
the room is assessed according
to a different scale based on this
setting.
Detailed information about the
operation of the motion sensor
can be found in the technical
documentation of the indoor
units.
01 High
02 Low
K6
Selection of allowed
operation modes when the
control sensor of the indoor
unit is set by C8 function
O
00 All modes allowed
This function is used to select
the operation modes in which
the setting of C8 (use of remote
control switch sensor or remote
sensor on THM4 to control the
indoor unit) is enabled.
01 Only cooling/dry allowed
02 Only heating allowed
03 All modes allowed
K7
Radiation Temperature
Sensor Calibration
O
00 Normal
Only available for units with
radiant sensor
01 Upper
02 Lower
03 Normal
K8 Not used -
00
- Use at 00 conditions
01
EN
SERVICE & INSTALLATION MENU
PMML0565 rev.1 - 04/202251