Instruction Manual
Table Of Contents
- 1 Safety summary
- 2 Switch Names and Functions
- 3 Operation
- 4 Icon Description
- 5 Function Menu
- 5.1 Simple Timer Setting
- 5.2 Operation Schedule Setting
- 5.3 Power Savings Setting
- 5.4 Night Quiet Operation
- 5.5 Power Saving/Night Quiet Schedule Setting
- 5.6 Power Consumption Display
- 5.7 Autoboost (QUICK MODE) Setting
- 5.8 Comfort Setting
- 5.9 Motion sensor setting
- 5.10 Setback Setting
- 5.11 Elevating Grille
- 5.12 Filter Reminder Reset Setting
- 5.13 FrostWash
- 5.14 Individual Louver Setting
- 5.15 Cancel Individual Louver Setting
- 5.16 Louver Open/Close
- 5.17 Ventilation
- 5.18 Total Heat Exchanger Setting
- 6 Service & installation menu
- 6.1 Installation menu
- 6.1.1 Test Run
- 6.1.2 Function selection
- 6.1.3 Thermistor Selection
- 6.1.4 Input / Output Setting
- 6.1.5 Thermistor Calibration in Controller
- 6.1.6 Fan Speed at Cooling Thermo-OFF
- 6.1.7 Fan Speed at Heating Thermo-OFF
- 6.1.8 Indoor Unit Address Change
- 6.1.9 Address Check Operation
- 6.1.10 Address Initialization
- 6.1.11 Setting Initialization
- 6.1.12 Main Remote Setting
- 6.1.13 Priority Setting
- 6.1.14 Cancel Preheating Control
- 6.1.15 Elevating grille Setting
- 6.1.16 Power Up Setting
- 6.1.17 Setback Trigger Unit
- 6.1.18 Refrigerant Leak Sensor Setting
- 6.2 Service menu
- 6.3 Check Menu
- 6.1 Installation menu
- 7 Screen Display Setting menu
- 8 Contact Information menu
- 9 Hotel Mode Setting
- 10 In Alarm Condition
Element Optional function
Individual
setting
Settings Setting conditions Description
J4
Override of Start/Stop
prohibition at the remote
controller
X
00 Start/Stop allowed (Factory setting)
When there is a remote control
prohibition from a central control
device, this function overrides
this prohibition allowing the
operation of the Run/Stop
button of the remote control
switch.
Models:
RPF(I)-FSN2E
Not used. Use at 00 conditions
01
Start/Stop not allowed
! DANGER
Blocking of Start/Stop shall never be set
due to safety concerns.
02 Only Stop allowed
J5 Not used -
00
- Use at 00 conditions
01
J6 Error Sound X
00 Once
To produce a sound when unit is
on alarm.
01 Continuous
J7 Not used –
00
- Use at 00 conditions
01
J8 Eco-operation
(7)
X
00 Function disabled (factory setting)
When the unit is restarted by
the remote control switch, the
temperature automatically
changes to the setting
temperature of “F5” or “F6”.
Models:
RPF(I)-FSN2E
Not available, use at 00
conditions
01 Function enabled
J9 Not used -
00
- Use at 00 conditions
01
JA
Display of "Simple
maintenance display" menu
O
00 Function disabled (factory setting)
Enables the “Simple
maintenance display” menu.
Models:
RPF(I)-FSN2E
Not available, use at 00
conditions
01 Function enabled
Jb Not used –
00
- Use at 00 conditions
01
SERVICE & INSTALLATION MENU