Instruction Manual
Table Of Contents
- 1 Safety summary
- 2 Switch Names and Functions
- 3 Operation
- 4 Icon Description
- 5 Function Menu
- 5.1 Simple Timer Setting
- 5.2 Operation Schedule Setting
- 5.3 Power Savings Setting
- 5.4 Night Quiet Operation
- 5.5 Power Saving/Night Quiet Schedule Setting
- 5.6 Power Consumption Display
- 5.7 Autoboost (QUICK MODE) Setting
- 5.8 Comfort Setting
- 5.9 Motion sensor setting
- 5.10 Setback Setting
- 5.11 Elevating Grille
- 5.12 Filter Reminder Reset Setting
- 5.13 FrostWash
- 5.14 Individual Louver Setting
- 5.15 Cancel Individual Louver Setting
- 5.16 Louver Open/Close
- 5.17 Ventilation
- 5.18 Total Heat Exchanger Setting
- 6 Service & installation menu
- 6.1 Installation menu
- 6.1.1 Test Run
- 6.1.2 Function selection
- 6.1.3 Thermistor Selection
- 6.1.4 Input / Output Setting
- 6.1.5 Thermistor Calibration in Controller
- 6.1.6 Fan Speed at Cooling Thermo-OFF
- 6.1.7 Fan Speed at Heating Thermo-OFF
- 6.1.8 Indoor Unit Address Change
- 6.1.9 Address Check Operation
- 6.1.10 Address Initialization
- 6.1.11 Setting Initialization
- 6.1.12 Main Remote Setting
- 6.1.13 Priority Setting
- 6.1.14 Cancel Preheating Control
- 6.1.15 Elevating grille Setting
- 6.1.16 Power Up Setting
- 6.1.17 Setback Trigger Unit
- 6.1.18 Refrigerant Leak Sensor Setting
- 6.2 Service menu
- 6.3 Check Menu
- 6.1 Installation menu
- 7 Screen Display Setting menu
- 8 Contact Information menu
- 9 Hotel Mode Setting
- 10 In Alarm Condition
Element Optional function
Individual
setting
Settings Setting conditions Description
F4 Automatic reset time X
00 30 minutes (factory setting)
This function sets the automatic
reset time delay for function F3.
01 15 minutes
02 60 minutes
03 90 minutes
F5
Automatic reset temperature
for cooling
X
19 19°C
This function denes the default
temperature set point for the
automatic reset function F3 in
FAN/COOL/DRY modes.
20 20°C
21 21°C
·
·
·
·
·
·
24 24°C
25 25°C (factory setting)
26 26°C
·
·
·
·
·
·
28 28°C
29 29°C
30 30°C
F6
Automatic reset temperature
for heating
X
17 17°C
This function denes the default
temperature set point for the
automatic reset function F3 in
HEAT mode.
18 18°C
·
·
·
·
·
·
20 20°C
21 21°C (factory setting)
25 25°C
·
·
·
·
·
·
28 28°C
29 29°C
30 30°C
F7
Prevention of operation
stoppage due to wrong
operation of the remote
controller
X
00 Function disabled (factory setting)
Operation is stopped by
pressing the run/stop switch for
3 seconds.
01 Function enabled
F8
Lock function for operation
mode selection
X
00 Function disabled
This function is used to prevent
changes to the operation mode.
01 Function enabled (factory setting)
F9
Lock function for temperature
setting
X
00 Function disabled
This function is used to prevent
changes to the temperature
setting.
01 Function enabled (factory setting)
FA
Lock function for fan speed
selection
X
00 Function disabled
This function is used to prevent
changes to the fan speed.
01 Function enabled (factory setting)
Fb
Lock function for swing louver
operation
X
00 Function disabled
This function is used to prevent
changes to the automatic louver
operation.
01 Function enabled (factory setting)