Instruction Manual
Table Of Contents
- 1 Safety summary
- 2 Switch Names and Functions
- 3 Operation
- 4 Icon Description
- 5 Function Menu
- 5.1 Simple Timer Setting
- 5.2 Operation Schedule Setting
- 5.3 Power Savings Setting
- 5.4 Night Quiet Operation
- 5.5 Power Saving/Night Quiet Schedule Setting
- 5.6 Power Consumption Display
- 5.7 Autoboost (QUICK MODE) Setting
- 5.8 Comfort Setting
- 5.9 Motion sensor setting
- 5.10 Setback Setting
- 5.11 Elevating Grille
- 5.12 Filter Reminder Reset Setting
- 5.13 FrostWash
- 5.14 Individual Louver Setting
- 5.15 Cancel Individual Louver Setting
- 5.16 Louver Open/Close
- 5.17 Ventilation
- 5.18 Total Heat Exchanger Setting
- 6 Service & installation menu
- 6.1 Installation menu
- 6.1.1 Test Run
- 6.1.2 Function selection
- 6.1.3 Thermistor Selection
- 6.1.4 Input / Output Setting
- 6.1.5 Thermistor Calibration in Controller
- 6.1.6 Fan Speed at Cooling Thermo-OFF
- 6.1.7 Fan Speed at Heating Thermo-OFF
- 6.1.8 Indoor Unit Address Change
- 6.1.9 Address Check Operation
- 6.1.10 Address Initialization
- 6.1.11 Setting Initialization
- 6.1.12 Main Remote Setting
- 6.1.13 Priority Setting
- 6.1.14 Cancel Preheating Control
- 6.1.15 Elevating grille Setting
- 6.1.16 Power Up Setting
- 6.1.17 Setback Trigger Unit
- 6.1.18 Refrigerant Leak Sensor Setting
- 6.2 Service menu
- 6.3 Check Menu
- 6.1 Installation menu
- 7 Screen Display Setting menu
- 8 Contact Information menu
- 9 Hotel Mode Setting
- 10 In Alarm Condition
Element Optional function
Individual
setting
Settings Setting conditions Description
EF
Control in “Automatic” indoor
fan speed mode (supporting
High H)
Models:
RCI-FSR
RCIM-FSRE
RCD-FSR
RPC-FSR
RPI(L/H)-FSRE
RPI-FSN3(P)E(-f)
RPK-FSR(H)M
O
00 Function disabled
This function limits the speed
of the indoor fan when room
temperature is close to the
setting temperature, allowing to
reach High H speed.
01 Function enabled
F0 Not available –
“- -”
permanent
– –
F1
Automatic OFF timer setting
Models:
RCI-FSR
RPC-FSR
RPK-FSRM
RPI(L/H)-FSRE
RCD-FSR
RCIM-FSRE
RPI-FSN3(P)E(-f)
X
00 Function disabled (Factory setting)
This function sets an automatic
OFF timer to switch OFF the
indoor units controlled by the
remote control switch (when
the units have been started by
remote control).
(Do not set the values "0C"-"0F"
when two remote control switches
are used in the same remote
control group).
01 1 hour
02 2 hours
03 3 hours
04-24 (04-24) hours
0A 30 minutes
0B 90 minutes
0C 40 minutes
}
Do not set these
when two wired
controllers are used.
0D 45 minutes
0E 50 minutes
0F 55 minutes
Automatic OFF timer setting
Models:
RPF(I)-FSN2E
X
00 Function disabled (Factory setting)
This function is used to set the
automatic timer to switch off
when the unit has been started
by remote control.
01 1 hour
02 2 hours
03 3 hours
04-24 (04-24) hours
0A 30 minutes
0B 90 minutes
F2
Remote control primary-
secondary setting
X
00
Primary (main remote control)
(Factory setting)
This function is used to dene
which remote control switch is
used as primary or secondary,
when two remote controllers are
connected to one indoor unit.
01 Secondary (sub remote control)
F3
Automatic reset of setting
temperature
(6)
X
00 Function disabled (Factory setting)
This function is used to limit unit
operation and save energy.
The setting temperature is
automatically set to the value
dened with functions "F5" or
"F6", according to the current
operation mode, after the
time set with function "F4" has
passed since the last manual
change of setting temperature.
In case that the values of “F5”
or “F6” are out of the limits set
with functions "FC" and "Fd",
limitations set by "FC" and "Fd"
have priority.
01 Function enabled
EN
SERVICE & INSTALLATION MENU
PMML0565 rev.1 - 04/202247