Instruction Manual
Table Of Contents
- 1 Safety summary
- 2 Switch Names and Functions
- 3 Operation
- 4 Icon Description
- 5 Function Menu
- 5.1 Simple Timer Setting
- 5.2 Operation Schedule Setting
- 5.3 Power Savings Setting
- 5.4 Night Quiet Operation
- 5.5 Power Saving/Night Quiet Schedule Setting
- 5.6 Power Consumption Display
- 5.7 Autoboost (QUICK MODE) Setting
- 5.8 Comfort Setting
- 5.9 Motion sensor setting
- 5.10 Setback Setting
- 5.11 Elevating Grille
- 5.12 Filter Reminder Reset Setting
- 5.13 FrostWash
- 5.14 Individual Louver Setting
- 5.15 Cancel Individual Louver Setting
- 5.16 Louver Open/Close
- 5.17 Ventilation
- 5.18 Total Heat Exchanger Setting
- 6 Service & installation menu
- 6.1 Installation menu
- 6.1.1 Test Run
- 6.1.2 Function selection
- 6.1.3 Thermistor Selection
- 6.1.4 Input / Output Setting
- 6.1.5 Thermistor Calibration in Controller
- 6.1.6 Fan Speed at Cooling Thermo-OFF
- 6.1.7 Fan Speed at Heating Thermo-OFF
- 6.1.8 Indoor Unit Address Change
- 6.1.9 Address Check Operation
- 6.1.10 Address Initialization
- 6.1.11 Setting Initialization
- 6.1.12 Main Remote Setting
- 6.1.13 Priority Setting
- 6.1.14 Cancel Preheating Control
- 6.1.15 Elevating grille Setting
- 6.1.16 Power Up Setting
- 6.1.17 Setback Trigger Unit
- 6.1.18 Refrigerant Leak Sensor Setting
- 6.2 Service menu
- 6.3 Check Menu
- 6.1 Installation menu
- 7 Screen Display Setting menu
- 8 Contact Information menu
- 9 Hotel Mode Setting
- 10 In Alarm Condition
Element Optional function
Individual
setting
Settings Setting conditions Description
C7
Cancellation of forced
compressor operation for at
least 3 minutes
O
00 Function disabled (factory setting)
This function is available
depending on the setting of
function b3.
01
Function enabled
(Compressor operation during 3 minutes
is no longer forced)
Only for KPI-E4E and
KPI-X4E
CO
2
sensor enabled
00
Sensor non enabled (factory setting)
Via 7-segments display set the
option Ct (00: ON/OFF Sensor
(Default); 01: 4-20mA 02: 0-10V)
01 Sensor enabled/activated
C8
(1)
Control by the temperature
sensor of the remote control
switch.
(2)
? NOTE
The remote control switch
shall be installed in a proper
place for the correct detection
of room temperature by its
temperature sensor.
O
00
Control by the air inlet sensor of indoor
units (factory setting)
This function species the
temperature sensor to be used
as control sensor by the indoor
unit.
01
Control by the temperature sensor of the
remote control switch
02
Control by the average value of the
air inlet sensor of indoor units and the
temperature sensor of the remote control
switch
(Air inlet + Remote control switch)/2
Control sensor when a
remote sensor is connected
to the THM4 connector in the
indoor unit PCB.
(3)
? NOTE
The remote sensor shall be
installed in a proper place for
the correct detection of room
temperature.
Model
RPF(I)-FSN2E
O
00, 01, 02
When a remote temperature sensor is
connected to THM4 on indoor unit main
PCB, this remote temperature sensor is
used as control sensor, whichever the
setting for C8 (factory setting C8=00)
Control sensor when a
remote sensor is connected
to the THM4 connector in the
indoor unit PCB.
(3)
? NOTE
The remote sensor shall be
installed in a proper place for
the correct detection of room
temperature.
All indoor units except
RPF(I)-FSN2E
00, 02
Air temperature control using the average
value of the air inlet thermistor and the
remote controller sensor (factory setting
C8=00)
(Air inlet + Remote sensor)/2
01
Air temperature control using the remote
sensor
C9 Not available –
“- -”
permanent
– –
CA Not available –
“- -”
permanent
– –
Cb
Selection of forced stoppage
logic
X
00
Forced stoppage input: A contact,
normally open contact (factory setting)
This function determines the
logic operation for the forced
stoppage contacts.
01
Forced stoppage input: B contact,
normally closed contact
EN
SERVICE & INSTALLATION MENU
PMML0565 rev.1 - 04/202243