Instruction Manual

Table Of Contents
Table A. Optional Setting Items for Function Selection
Element Optional function
Individual
setting
Settings Setting conditions Description
b1
Heating temperature
compensation
Models:
All indoor units except
RPF(I)-FSN2E
O
00
Normal (factory setting)
(Setting Temperature + 4°C)
This function is used to adjust
the temperature difference
between the temperature read
by the inlet sensor and the real
room temperature.
This is useful when the inlet air
thermistor is not placed inside
the indoor unit or due to uneven
heat load.
Note:
The “02”, “03”, “04” settings
may not be available
depending on the type of
indoor unit.
This setting shall be
performed separately for
each indoor unit, even in
case that multiple indoor
units are connected to one
remote controller.
01
No compensation
(Setting Temperature)
02 Setting Temperature + 2°C
03 Setting Temperature + 3°C
04 Setting Temperature + 1°C
Heating temperature
compensation
Models:
RPF(I)-FSN2E
O
00
RPF(I)-FSN2E: Normal (factory setting)
(Setting Temperature + 2°C)
01 No compensation (Setting Temperature)
02 Setting Temperature + 2°C
b2
Circulation function at heating
Thermo-OFF
O
00 Function disabled (factory setting)
This function keeps the fan
running during the Thermo-OFF
sequence, at the fan speed set
on the remote control switch, to
prevent the stratication of air in
the room.
01 Function enabled
b3 Not used
00
- Use at 00 conditions
01
b4
Change of lter cleaning
period
O
00 Standard (1200 hours)
This function is used to modify
the period of operation after
which the air lter cleaning
indication is shown in the
remote control.
For RPK-FSR(H)M models,
the factory setting is b4=00:
Standard setting 200 hours.
01 100 hours
02 1200 hours (factory setting)
03 2500 hours
04 No indication
b5
Locking of operation mode
(Not available for models
KPI-E4)
X
00 Function disabled (factory setting)
This function prevents the
modication of the operation
mode of the unit from the
remote controller and from
central controls, once it has
been selected.
01 Function enabled
b6
Locking of temperature
setting
X
00 Function disabled (factory setting)
This function prevents the
modication of the setting
temperature of the unit from
the remote controller and from
central controls, once it has
been selected.
01 Function enabled
b7
Setting operation mode as
cooling only
(Not available for models
KPI-E4)
X
00 Function disabled (factory setting)
This function is used to limit the
operation mode to cooling only
and to prevent heating mode
from being enabled.
01 Function enabled
b8
Automatic COOL/HEAT
operation
(Not available for models
KPI-E4)
X
00 Function disabled (factory setting)
This function enables the
selection of Auto cool/heat
operation mode. If the function
is not activated, Auto cool/heat
mode cannot be selected on the
remote control switch.
01 Function enabled
EN
SERVICE & INSTALLATION MENU